Kabelarea för 350 Ampere vid 100 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 350 A över 100 m vid 400V.
Copper Cable (≤3% Drop)185 mm²Drop: 7.01V (1.75%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 7.13V (1.78%)
Voltage at Load393.0 VLine Loss: 4251.1 W
Max Power & Breaker242.49 kW350A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 100m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 864.87 V (216.22%) | 0.0 V | 1426.63 V (356.66%) | 524300.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 518.92 V (129.73%) | 0.0 V | 855.98 V (213.99%) | 314580.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 324.33 V (81.08%) | 75.7 V | 534.99 V (133.75%) | 196612.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 216.22 V (54.05%) | 183.8 V | 356.66 V (89.16%) | 131075.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 129.73 V (32.43%) | 270.3 V | 213.99 V (53.5%) | 78645.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 81.08 V (20.27%) | 318.9 V | 133.75 V (33.44%) | 49153.1 W | Drop High |
| 25 mm² | 101 A | 78 A | 51.89 V (12.97%) | 348.1 V | 85.6 V (21.4%) | 31458.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 37.07 V (9.27%) | 362.9 V | 61.14 V (15.29%) | 22470.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 25.95 V (6.49%) | 374.1 V | 42.8 V (10.7%) | 15729.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 18.53 V (4.63%) | 381.5 V | 30.57 V (7.64%) | 11235.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 13.66 V (3.41%) | 386.3 V | 22.53 V (5.63%) | 8278.4 W | Drop High |
| 120 mm² | 269 A | 210 A | 10.81 V (2.7%) | 389.2 V | 17.83 V (4.46%) | 6553.7 W | Drop High |
| 150 mm² | 309 A | 241 A | 8.65 V (2.16%) | 391.4 V | 14.27 V (3.57%) | 5243.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 7.01 V (1.75%) | 393.0 V | 11.57 V (2.89%) | 4251.1 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 5.41 V (1.35%) | 394.6 V | 8.92 V (2.23%) | 3276.9 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 4.32 V (1.08%) | 395.7 V | 7.13 V (1.78%) | 2621.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 3.24 V (0.81%) | 396.8 V | 5.35 V (1.34%) | 1966.1 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 350 Ampere vid 100 Meter (400V)
Vilken kabelarea krävs för 350A vid 100 meter (400V)?
För 350 Ampere över 100 meter vid 400V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (7.01V / 1.75%).
Hur stor effekt motsvarar 350A vid 400V?
Det motsvarar 242.49 kW med en rekommenderad säkring på 350A.
Related Lengths & Currents (400V)
350A · 5m (400V)350A · 10m (400V)350A · 15m (400V)350A · 20m (400V)350A · 25m (400V)350A · 30m (400V)350A · 35m (400V)350A · 40m (400V)350A · 45m (400V)350A · 50m (400V)350A · 60m (400V)350A · 70m (400V)10A · 100m (400V)16A · 100m (400V)20A · 100m (400V)25A · 100m (400V)32A · 100m (400V)40A · 100m (400V)50A · 100m (400V)63A · 100m (400V)80A · 100m (400V)100A · 100m (400V)125A · 100m (400V)160A · 100m (400V)200A · 100m (400V)