Kabelarea för 350 Ampere vid 15 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 350 A över 15 m vid 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 1.05V (0.26%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.07V (0.27%)
Voltage at Load398.9 VLine Loss: 637.7 W
Max Power & Breaker242.49 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A129.73 V (32.43%)270.3 V213.99 V (53.5%)78645.0 WDrop High
2.5 mm²24 A18 A77.84 V (19.46%)322.2 V128.4 V (32.1%)47187.0 WDrop High
4 mm²32 A25 A48.65 V (12.16%)351.4 V80.25 V (20.06%)29491.9 WDrop High
6 mm²41 A32 A32.43 V (8.11%)367.6 V53.5 V (13.37%)19661.2 WDrop High
10 mm²57 A44 A19.46 V (4.86%)380.5 V32.1 V (8.02%)11796.8 WDrop High
16 mm²76 A59 A12.16 V (3.04%)387.8 V20.06 V (5.02%)7373.0 WDrop High
25 mm²101 A78 A7.78 V (1.95%)392.2 V12.84 V (3.21%)4718.7 WDrop High
35 mm²125 A97 A5.56 V (1.39%)394.4 V9.17 V (2.29%)3370.5 WDrop High
50 mm²151 A118 A3.89 V (0.97%)396.1 V6.42 V (1.6%)2359.3 WDrop High
70 mm²192 A150 A2.78 V (0.69%)397.2 V4.59 V (1.15%)1685.2 WDrop High
95 mm²232 A181 A2.05 V (0.51%)398.0 V3.38 V (0.84%)1241.8 WDrop High
120 mm²269 A210 A1.62 V (0.41%)398.4 V2.67 V (0.67%)983.1 WDrop High
150 mm²309 A241 A1.3 V (0.32%)398.7 V2.14 V (0.53%)786.5 WDrop High
185 mm²353 A275 A1.05 V (0.26%)398.9 V1.74 V (0.43%)637.7 W✓ OK (≤3%)
240 mm²415 A324 A0.81 V (0.2%)399.2 V1.34 V (0.33%)491.5 W✓ OK (≤3%)
300 mm²477 A372 A0.65 V (0.16%)399.4 V1.07 V (0.27%)393.2 W✓ OK (≤3%)
400 mm²570 A445 A0.49 V (0.12%)399.5 V0.8 V (0.2%)294.9 W✓ OK (≤3%)

FAQ — Kabelarea för 350 Ampere vid 15 Meter (400V)

Vilken kabelarea krävs för 350A vid 15 meter (400V)?

För 350 Ampere över 15 meter vid 400V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (1.05V / 0.26%).

Hur stor effekt motsvarar 350A vid 400V?

Det motsvarar 242.49 kW med en rekommenderad säkring på 350A.