Kabelarea för 400 Ampere vid 45 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 400 A över 45 m vid 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 2.78V (0.69%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.75V (0.69%)
Voltage at Load397.2 VLine Loss: 1926.0 W
Max Power & Breaker277.13 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A444.79 V (111.2%)0.0 V733.7 V (183.42%)308160.0 WDrop High
2.5 mm²24 A18 A266.87 V (66.72%)133.1 V440.22 V (110.05%)184896.0 WDrop High
4 mm²32 A25 A166.8 V (41.7%)233.2 V275.14 V (68.78%)115560.0 WDrop High
6 mm²41 A32 A111.2 V (27.8%)288.8 V183.42 V (45.86%)77040.0 WDrop High
10 mm²57 A44 A66.72 V (16.68%)333.3 V110.05 V (27.51%)46224.0 WDrop High
16 mm²76 A59 A41.7 V (10.42%)358.3 V68.78 V (17.2%)28890.0 WDrop High
25 mm²101 A78 A26.69 V (6.67%)373.3 V44.02 V (11.01%)18489.6 WDrop High
35 mm²125 A97 A19.06 V (4.77%)380.9 V31.44 V (7.86%)13206.9 WDrop High
50 mm²151 A118 A13.34 V (3.34%)386.7 V22.01 V (5.5%)9244.8 WDrop High
70 mm²192 A150 A9.53 V (2.38%)390.5 V15.72 V (3.93%)6603.4 WDrop High
95 mm²232 A181 A7.02 V (1.76%)393.0 V11.58 V (2.9%)4865.7 WDrop High
120 mm²269 A210 A5.56 V (1.39%)394.4 V9.17 V (2.29%)3852.0 WDrop High
150 mm²309 A241 A4.45 V (1.11%)395.6 V7.34 V (1.83%)3081.6 WDrop High
185 mm²353 A275 A3.61 V (0.9%)396.4 V5.95 V (1.49%)2498.6 WDrop High
240 mm²415 A324 A2.78 V (0.69%)397.2 V4.59 V (1.15%)1926.0 W✓ OK (≤3%)
300 mm²477 A372 A2.22 V (0.56%)397.8 V3.67 V (0.92%)1540.8 W✓ OK (≤3%)
400 mm²570 A445 A1.67 V (0.42%)398.3 V2.75 V (0.69%)1155.6 W✓ OK (≤3%)

FAQ — Kabelarea för 400 Ampere vid 45 Meter (400V)

Vilken kabelarea krävs för 400A vid 45 meter (400V)?

För 400 Ampere över 45 meter vid 400V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (2.78V / 0.69%).

Hur stor effekt motsvarar 400A vid 400V?

Det motsvarar 277.13 kW med en rekommenderad säkring på 400A.