⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 45 Ampere vid 45 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 45 A över 45 m vid 230V.

Copper Cable (≤3% Drop)16 mm²Drop: 5.42V (2.36%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 5.72V (2.49%)
Voltage at Load224.6 VLine Loss: 243.8 W
Max Power & Breaker10.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A57.78 V (25.12%)172.2 V95.31 V (41.44%)2600.1 WDrop High
2.5 mm²24 A18 A34.67 V (15.07%)195.3 V57.19 V (24.86%)1560.1 WDrop High
4 mm²32 A25 A21.67 V (9.42%)208.3 V35.74 V (15.54%)975.0 WDrop High
6 mm²41 A32 A14.45 V (6.28%)215.6 V23.83 V (10.36%)650.0 WDrop High
10 mm²57 A44 A8.67 V (3.77%)221.3 V14.3 V (6.22%)390.0 W~ ≤5%
16 mm²76 A59 A5.42 V (2.36%)224.6 V8.94 V (3.88%)243.8 W✓ OK (≤3%)
25 mm²101 A78 A3.47 V (1.51%)226.5 V5.72 V (2.49%)156.0 W✓ OK (≤3%)
35 mm²125 A97 A2.48 V (1.08%)227.5 V4.08 V (1.78%)111.4 W✓ OK (≤3%)
50 mm²151 A118 A1.73 V (0.75%)228.3 V2.86 V (1.24%)78.0 W✓ OK (≤3%)
70 mm²192 A150 A1.24 V (0.54%)228.8 V2.04 V (0.89%)55.7 W✓ OK (≤3%)
95 mm²232 A181 A0.91 V (0.4%)229.1 V1.5 V (0.65%)41.1 W✓ OK (≤3%)
120 mm²269 A210 A0.72 V (0.31%)229.3 V1.19 V (0.52%)32.5 W✓ OK (≤3%)
150 mm²309 A241 A0.58 V (0.25%)229.4 V0.95 V (0.41%)26.0 W✓ OK (≤3%)
185 mm²353 A275 A0.47 V (0.2%)229.5 V0.77 V (0.34%)21.1 W✓ OK (≤3%)
240 mm²415 A324 A0.36 V (0.16%)229.6 V0.6 V (0.26%)16.3 W✓ OK (≤3%)
300 mm²477 A372 A0.29 V (0.13%)229.7 V0.48 V (0.21%)13.0 W✓ OK (≤3%)
400 mm²570 A445 A0.22 V (0.09%)229.8 V0.36 V (0.16%)9.8 W✓ OK (≤3%)

FAQ — Kabelarea för 45 Ampere vid 45 Meter (230V)

Vilken kabelarea krävs för 45A vid 45 meter (230V)?

För 45 Ampere över 45 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (5.42V / 2.36%).

Hur stor effekt motsvarar 45A vid 230V?

Det motsvarar 10.35 kW med en rekommenderad säkring på 45A.