Kabelarea för 45 Ampere vid 30 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 45 A över 30 m vid 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.78V (2.51%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.96V (2.59%)
Voltage at Load224.2 VLine Loss: 260.0 W
Max Power & Breaker10.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A38.52 V (16.75%)191.5 V63.54 V (27.63%)1733.4 WDrop High
2.5 mm²24 A18 A23.11 V (10.05%)206.9 V38.12 V (16.58%)1040.0 WDrop High
4 mm²32 A25 A14.45 V (6.28%)215.6 V23.83 V (10.36%)650.0 WDrop High
6 mm²41 A32 A9.63 V (4.19%)220.4 V15.88 V (6.91%)433.3 WDrop High
10 mm²57 A44 A5.78 V (2.51%)224.2 V9.53 V (4.14%)260.0 W✓ OK (≤3%)
16 mm²76 A59 A3.61 V (1.57%)226.4 V5.96 V (2.59%)162.5 W✓ OK (≤3%)
25 mm²101 A78 A2.31 V (1.0%)227.7 V3.81 V (1.66%)104.0 W✓ OK (≤3%)
35 mm²125 A97 A1.65 V (0.72%)228.3 V2.72 V (1.18%)74.3 W✓ OK (≤3%)
50 mm²151 A118 A1.16 V (0.5%)228.8 V1.91 V (0.83%)52.0 W✓ OK (≤3%)
70 mm²192 A150 A0.83 V (0.36%)229.2 V1.36 V (0.59%)37.1 W✓ OK (≤3%)
95 mm²232 A181 A0.61 V (0.26%)229.4 V1.0 V (0.44%)27.4 W✓ OK (≤3%)
120 mm²269 A210 A0.48 V (0.21%)229.5 V0.79 V (0.35%)21.7 W✓ OK (≤3%)
150 mm²309 A241 A0.39 V (0.17%)229.6 V0.64 V (0.28%)17.3 W✓ OK (≤3%)
185 mm²353 A275 A0.31 V (0.14%)229.7 V0.52 V (0.22%)14.1 W✓ OK (≤3%)
240 mm²415 A324 A0.24 V (0.1%)229.8 V0.4 V (0.17%)10.8 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.08%)229.8 V0.32 V (0.14%)8.7 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.06%)229.9 V0.24 V (0.1%)6.5 W✓ OK (≤3%)

FAQ — Kabelarea för 45 Ampere vid 30 Meter (230V)

Vilken kabelarea krävs för 45A vid 30 meter (230V)?

För 45 Ampere över 30 meter vid 230V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (5.78V / 2.51%).

Hur stor effekt motsvarar 45A vid 230V?

Det motsvarar 10.35 kW med en rekommenderad säkring på 45A.