Kabelarea för 450 Ampere vid 45 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 450 A över 45 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 2.89V (1.26%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.57V (1.55%)
Voltage at Load227.1 VLine Loss: 1300.0 W
Max Power & Breaker103.5 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A577.8 V (251.22%)0.0 V953.1 V (414.39%)260010.0 WDrop High
2.5 mm²24 A18 A346.68 V (150.73%)0.0 V571.86 V (248.63%)156006.0 WDrop High
4 mm²32 A25 A216.67 V (94.21%)13.3 V357.41 V (155.4%)97503.8 WDrop High
6 mm²41 A32 A144.45 V (62.8%)85.5 V238.27 V (103.6%)65002.5 WDrop High
10 mm²57 A44 A86.67 V (37.68%)143.3 V142.97 V (62.16%)39001.5 WDrop High
16 mm²76 A59 A54.17 V (23.55%)175.8 V89.35 V (38.85%)24375.9 WDrop High
25 mm²101 A78 A34.67 V (15.07%)195.3 V57.19 V (24.86%)15600.6 WDrop High
35 mm²125 A97 A24.76 V (10.77%)205.2 V40.85 V (17.76%)11143.3 WDrop High
50 mm²151 A118 A17.33 V (7.54%)212.7 V28.59 V (12.43%)7800.3 WDrop High
70 mm²192 A150 A12.38 V (5.38%)217.6 V20.42 V (8.88%)5571.6 WDrop High
95 mm²232 A181 A9.12 V (3.97%)220.9 V15.05 V (6.54%)4105.4 WDrop High
120 mm²269 A210 A7.22 V (3.14%)222.8 V11.91 V (5.18%)3250.1 WDrop High
150 mm²309 A241 A5.78 V (2.51%)224.2 V9.53 V (4.14%)2600.1 WDrop High
185 mm²353 A275 A4.68 V (2.04%)225.3 V7.73 V (3.36%)2108.2 WDrop High
240 mm²415 A324 A3.61 V (1.57%)226.4 V5.96 V (2.59%)1625.1 WDrop High
300 mm²477 A372 A2.89 V (1.26%)227.1 V4.77 V (2.07%)1300.0 W✓ OK (≤3%)
400 mm²570 A445 A2.17 V (0.94%)227.8 V3.57 V (1.55%)975.0 W✓ OK (≤3%)

FAQ — Kabelarea för 450 Ampere vid 45 Meter (230V)

Vilken kabelarea krävs för 450A vid 45 meter (230V)?

För 450 Ampere över 45 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (2.89V / 1.26%).

Hur stor effekt motsvarar 450A vid 230V?

Det motsvarar 103.5 kW med en rekommenderad säkring på 450A.