Kabelarea för 450 Ampere vid 70 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 450 A över 70 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 4.49V (1.95%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.56V (2.42%)
Voltage at Load225.5 VLine Loss: 2022.3 W
Max Power & Breaker103.5 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A898.8 V (390.78%)0.0 V1482.6 V (644.61%)404460.0 WDrop High
2.5 mm²24 A18 A539.28 V (234.47%)0.0 V889.56 V (386.77%)242676.0 WDrop High
4 mm²32 A25 A337.05 V (146.54%)0.0 V555.98 V (241.73%)151672.5 WDrop High
6 mm²41 A32 A224.7 V (97.7%)5.3 V370.65 V (161.15%)101115.0 WDrop High
10 mm²57 A44 A134.82 V (58.62%)95.2 V222.39 V (96.69%)60669.0 WDrop High
16 mm²76 A59 A84.26 V (36.64%)145.7 V138.99 V (60.43%)37918.1 WDrop High
25 mm²101 A78 A53.93 V (23.45%)176.1 V88.96 V (38.68%)24267.6 WDrop High
35 mm²125 A97 A38.52 V (16.75%)191.5 V63.54 V (27.63%)17334.0 WDrop High
50 mm²151 A118 A26.96 V (11.72%)203.0 V44.48 V (19.34%)12133.8 WDrop High
70 mm²192 A150 A19.26 V (8.37%)210.7 V31.77 V (13.81%)8667.0 WDrop High
95 mm²232 A181 A14.19 V (6.17%)215.8 V23.41 V (10.18%)6386.2 WDrop High
120 mm²269 A210 A11.24 V (4.88%)218.8 V18.53 V (8.06%)5055.8 WDrop High
150 mm²309 A241 A8.99 V (3.91%)221.0 V14.83 V (6.45%)4044.6 WDrop High
185 mm²353 A275 A7.29 V (3.17%)222.7 V12.02 V (5.23%)3279.4 WDrop High
240 mm²415 A324 A5.62 V (2.44%)224.4 V9.27 V (4.03%)2527.9 WDrop High
300 mm²477 A372 A4.49 V (1.95%)225.5 V7.41 V (3.22%)2022.3 W✓ OK (≤3%)
400 mm²570 A445 A3.37 V (1.47%)226.6 V5.56 V (2.42%)1516.7 W✓ OK (≤3%)

FAQ — Kabelarea för 450 Ampere vid 70 Meter (230V)

Vilken kabelarea krävs för 450A vid 70 meter (230V)?

För 450 Ampere över 70 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (4.49V / 1.95%).

Hur stor effekt motsvarar 450A vid 230V?

Det motsvarar 103.5 kW med en rekommenderad säkring på 450A.