Kabelarea för 500 Ampere vid 500 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 500 A över 500 m vid 230V.

Copper Cable (≤3% Drop)4× 400 mm²Drop: 6.69V (2.91%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 44.12V (19.18%)
Voltage at Load223.3 VLine Loss: 3343.8 W
Max Power & Breaker115.0 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7133.33 V (3101.45%)0.0 V11766.67 V (5115.94%)3566666.7 WDrop High
2.5 mm²24 A18 A4280.0 V (1860.87%)0.0 V7060.0 V (3069.57%)2140000.0 WDrop High
4 mm²32 A25 A2675.0 V (1163.04%)0.0 V4412.5 V (1918.48%)1337500.0 WDrop High
6 mm²41 A32 A1783.33 V (775.36%)0.0 V2941.67 V (1278.99%)891666.7 WDrop High
10 mm²57 A44 A1070.0 V (465.22%)0.0 V1765.0 V (767.39%)535000.0 WDrop High
16 mm²76 A59 A668.75 V (290.76%)0.0 V1103.12 V (479.62%)334375.0 WDrop High
25 mm²101 A78 A428.0 V (186.09%)0.0 V706.0 V (306.96%)214000.0 WDrop High
35 mm²125 A97 A305.71 V (132.92%)0.0 V504.29 V (219.25%)152857.1 WDrop High
50 mm²151 A118 A214.0 V (93.04%)16.0 V353.0 V (153.48%)107000.0 WDrop High
70 mm²192 A150 A152.86 V (66.46%)77.1 V252.14 V (109.63%)76428.6 WDrop High
95 mm²232 A181 A112.63 V (48.97%)117.4 V185.79 V (80.78%)56315.8 WDrop High
120 mm²269 A210 A89.17 V (38.77%)140.8 V147.08 V (63.95%)44583.3 WDrop High
150 mm²309 A241 A71.33 V (31.01%)158.7 V117.67 V (51.16%)35666.7 WDrop High
185 mm²353 A275 A57.84 V (25.15%)172.2 V95.41 V (41.48%)28918.9 WDrop High
240 mm²415 A324 A44.58 V (19.38%)185.4 V73.54 V (31.97%)22291.7 WDrop High
300 mm²477 A372 A35.67 V (15.51%)194.3 V58.83 V (25.58%)17833.3 WDrop High
400 mm²570 A445 A26.75 V (11.63%)203.2 V44.12 V (19.18%)13375.0 WDrop High

FAQ — Kabelarea för 500 Ampere vid 500 Meter (230V)

Vilken kabelarea krävs för 500A vid 500 meter (230V)?

För 500 Ampere över 500 meter vid 230V rekommenderas 4× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.69V / 2.91%).

Hur stor effekt motsvarar 500A vid 230V?

Det motsvarar 115.0 kW med en rekommenderad säkring på 500A.