Kabelarea för 650 Ampere vid 150 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 650 A över 150 m vid 230V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.21V (2.27%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 17.21V (7.48%)
Voltage at Load224.8 VLine Loss: 3390.6 W
Max Power & Breaker149.5 kW700A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 150m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2782.0 V (1209.57%) | 0.0 V | 4589.0 V (1995.22%) | 1808300.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1669.2 V (725.74%) | 0.0 V | 2753.4 V (1197.13%) | 1084980.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1043.25 V (453.59%) | 0.0 V | 1720.88 V (748.21%) | 678112.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 695.5 V (302.39%) | 0.0 V | 1147.25 V (498.8%) | 452075.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 417.3 V (181.43%) | 0.0 V | 688.35 V (299.28%) | 271245.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 260.81 V (113.4%) | 0.0 V | 430.22 V (187.05%) | 169528.1 W | Drop High |
| 25 mm² | 101 A | 78 A | 166.92 V (72.57%) | 63.1 V | 275.34 V (119.71%) | 108498.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 119.23 V (51.84%) | 110.8 V | 196.67 V (85.51%) | 77498.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 83.46 V (36.29%) | 146.5 V | 137.67 V (59.86%) | 54249.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 59.61 V (25.92%) | 170.4 V | 98.34 V (42.75%) | 38749.3 W | Drop High |
| 95 mm² | 232 A | 181 A | 43.93 V (19.1%) | 186.1 V | 72.46 V (31.5%) | 28552.1 W | Drop High |
| 120 mm² | 269 A | 210 A | 34.77 V (15.12%) | 195.2 V | 57.36 V (24.94%) | 22603.8 W | Drop High |
| 150 mm² | 309 A | 241 A | 27.82 V (12.1%) | 202.2 V | 45.89 V (19.95%) | 18083.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 22.56 V (9.81%) | 207.4 V | 37.21 V (16.18%) | 14661.9 W | Drop High |
| 240 mm² | 415 A | 324 A | 17.39 V (7.56%) | 212.6 V | 28.68 V (12.47%) | 11301.9 W | Drop High |
| 300 mm² | 477 A | 372 A | 13.91 V (6.05%) | 216.1 V | 22.95 V (9.98%) | 9041.5 W | Drop High |
| 400 mm² | 570 A | 445 A | 10.43 V (4.54%) | 219.6 V | 17.21 V (7.48%) | 6781.1 W | Drop High |
FAQ — Kabelarea för 650 Ampere vid 150 Meter (230V)
Vilken kabelarea krävs för 650A vid 150 meter (230V)?
För 650 Ampere över 150 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.21V / 2.27%).
Hur stor effekt motsvarar 650A vid 230V?
Det motsvarar 149.5 kW med en rekommenderad säkring på 700A.
Related Lengths & Currents (230V)
650A · 5m (230V)650A · 10m (230V)650A · 15m (230V)650A · 20m (230V)650A · 25m (230V)650A · 30m (230V)650A · 35m (230V)650A · 40m (230V)650A · 45m (230V)650A · 50m (230V)650A · 60m (230V)650A · 70m (230V)10A · 150m (230V)16A · 150m (230V)20A · 150m (230V)25A · 150m (230V)32A · 150m (230V)40A · 150m (230V)50A · 150m (230V)63A · 150m (230V)80A · 150m (230V)100A · 150m (230V)125A · 150m (230V)160A · 150m (230V)200A · 150m (230V)