Kabelarea för 650 Ampere vid 150 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 650 A över 150 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.21V (2.27%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 17.21V (7.48%)
Voltage at Load224.8 VLine Loss: 3390.6 W
Max Power & Breaker149.5 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2782.0 V (1209.57%)0.0 V4589.0 V (1995.22%)1808300.0 WDrop High
2.5 mm²24 A18 A1669.2 V (725.74%)0.0 V2753.4 V (1197.13%)1084980.0 WDrop High
4 mm²32 A25 A1043.25 V (453.59%)0.0 V1720.88 V (748.21%)678112.5 WDrop High
6 mm²41 A32 A695.5 V (302.39%)0.0 V1147.25 V (498.8%)452075.0 WDrop High
10 mm²57 A44 A417.3 V (181.43%)0.0 V688.35 V (299.28%)271245.0 WDrop High
16 mm²76 A59 A260.81 V (113.4%)0.0 V430.22 V (187.05%)169528.1 WDrop High
25 mm²101 A78 A166.92 V (72.57%)63.1 V275.34 V (119.71%)108498.0 WDrop High
35 mm²125 A97 A119.23 V (51.84%)110.8 V196.67 V (85.51%)77498.6 WDrop High
50 mm²151 A118 A83.46 V (36.29%)146.5 V137.67 V (59.86%)54249.0 WDrop High
70 mm²192 A150 A59.61 V (25.92%)170.4 V98.34 V (42.75%)38749.3 WDrop High
95 mm²232 A181 A43.93 V (19.1%)186.1 V72.46 V (31.5%)28552.1 WDrop High
120 mm²269 A210 A34.77 V (15.12%)195.2 V57.36 V (24.94%)22603.8 WDrop High
150 mm²309 A241 A27.82 V (12.1%)202.2 V45.89 V (19.95%)18083.0 WDrop High
185 mm²353 A275 A22.56 V (9.81%)207.4 V37.21 V (16.18%)14661.9 WDrop High
240 mm²415 A324 A17.39 V (7.56%)212.6 V28.68 V (12.47%)11301.9 WDrop High
300 mm²477 A372 A13.91 V (6.05%)216.1 V22.95 V (9.98%)9041.5 WDrop High
400 mm²570 A445 A10.43 V (4.54%)219.6 V17.21 V (7.48%)6781.1 WDrop High

FAQ — Kabelarea för 650 Ampere vid 150 Meter (230V)

Vilken kabelarea krävs för 650A vid 150 meter (230V)?

För 650 Ampere över 150 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.21V / 2.27%).

Hur stor effekt motsvarar 650A vid 230V?

Det motsvarar 149.5 kW med en rekommenderad säkring på 700A.