Kabelarea för 650 Ampere vid 20 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 650 A över 20 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.69V (0.3%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.29V (1.0%)
Voltage at Load229.3 VLine Loss: 452.1 W
Max Power & Breaker149.5 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A370.93 V (161.28%)0.0 V611.87 V (266.03%)241106.7 WDrop High
2.5 mm²24 A18 A222.56 V (96.77%)7.4 V367.12 V (159.62%)144664.0 WDrop High
4 mm²32 A25 A139.1 V (60.48%)90.9 V229.45 V (99.76%)90415.0 WDrop High
6 mm²41 A32 A92.73 V (40.32%)137.3 V152.97 V (66.51%)60276.7 WDrop High
10 mm²57 A44 A55.64 V (24.19%)174.4 V91.78 V (39.9%)36166.0 WDrop High
16 mm²76 A59 A34.77 V (15.12%)195.2 V57.36 V (24.94%)22603.8 WDrop High
25 mm²101 A78 A22.26 V (9.68%)207.7 V36.71 V (15.96%)14466.4 WDrop High
35 mm²125 A97 A15.9 V (6.91%)214.1 V26.22 V (11.4%)10333.1 WDrop High
50 mm²151 A118 A11.13 V (4.84%)218.9 V18.36 V (7.98%)7233.2 WDrop High
70 mm²192 A150 A7.95 V (3.46%)222.1 V13.11 V (5.7%)5166.6 WDrop High
95 mm²232 A181 A5.86 V (2.55%)224.1 V9.66 V (4.2%)3806.9 WDrop High
120 mm²269 A210 A4.64 V (2.02%)225.4 V7.65 V (3.33%)3013.8 WDrop High
150 mm²309 A241 A3.71 V (1.61%)226.3 V6.12 V (2.66%)2411.1 WDrop High
185 mm²353 A275 A3.01 V (1.31%)227.0 V4.96 V (2.16%)1954.9 WDrop High
240 mm²415 A324 A2.32 V (1.01%)227.7 V3.82 V (1.66%)1506.9 WDrop High
300 mm²477 A372 A1.85 V (0.81%)228.1 V3.06 V (1.33%)1205.5 WDrop High
400 mm²570 A445 A1.39 V (0.6%)228.6 V2.29 V (1.0%)904.1 WDrop High

FAQ — Kabelarea för 650 Ampere vid 20 Meter (230V)

Vilken kabelarea krävs för 650A vid 20 meter (230V)?

För 650 Ampere över 20 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (0.69V / 0.3%).

Hur stor effekt motsvarar 650A vid 230V?

Det motsvarar 149.5 kW med en rekommenderad säkring på 700A.