Kabelarea för 70 Ampere vid 70 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 70 A över 70 m vid 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 11.35V (2.84%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 11.98V (3.0%)
Voltage at Load388.6 VLine Loss: 1376.3 W
Max Power & Breaker48.5 kW70A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 70A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A121.08 V (30.27%)278.9 V199.73 V (49.93%)14680.4 WDrop High
2.5 mm²24 A18 A72.65 V (18.16%)327.4 V119.84 V (29.96%)8808.2 WDrop High
4 mm²32 A25 A45.41 V (11.35%)354.6 V74.9 V (18.72%)5505.1 WDrop High
6 mm²41 A32 A30.27 V (7.57%)369.7 V49.93 V (12.48%)3670.1 WDrop High
10 mm²57 A44 A18.16 V (4.54%)381.8 V29.96 V (7.49%)2202.1 WDrop High
16 mm²76 A59 A11.35 V (2.84%)388.6 V18.72 V (4.68%)1376.3 W✓ OK (≤3%)
25 mm²101 A78 A7.26 V (1.82%)392.7 V11.98 V (3.0%)880.8 W✓ OK (≤3%)
35 mm²125 A97 A5.19 V (1.3%)394.8 V8.56 V (2.14%)629.2 W✓ OK (≤3%)
50 mm²151 A118 A3.63 V (0.91%)396.4 V5.99 V (1.5%)440.4 W✓ OK (≤3%)
70 mm²192 A150 A2.59 V (0.65%)397.4 V4.28 V (1.07%)314.6 W✓ OK (≤3%)
95 mm²232 A181 A1.91 V (0.48%)398.1 V3.15 V (0.79%)231.8 W✓ OK (≤3%)
120 mm²269 A210 A1.51 V (0.38%)398.5 V2.5 V (0.62%)183.5 W✓ OK (≤3%)
150 mm²309 A241 A1.21 V (0.3%)398.8 V2.0 V (0.5%)146.8 W✓ OK (≤3%)
185 mm²353 A275 A0.98 V (0.25%)399.0 V1.62 V (0.4%)119.0 W✓ OK (≤3%)
240 mm²415 A324 A0.76 V (0.19%)399.2 V1.25 V (0.31%)91.8 W✓ OK (≤3%)
300 mm²477 A372 A0.61 V (0.15%)399.4 V1.0 V (0.25%)73.4 W✓ OK (≤3%)
400 mm²570 A445 A0.45 V (0.11%)399.5 V0.75 V (0.19%)55.1 W✓ OK (≤3%)

FAQ — Kabelarea för 70 Ampere vid 70 Meter (400V)

Vilken kabelarea krävs för 70A vid 70 meter (400V)?

För 70 Ampere över 70 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (11.35V / 2.84%).

Hur stor effekt motsvarar 70A vid 400V?

Det motsvarar 48.5 kW med en rekommenderad säkring på 70A.