Kabelarea för 200 Ampere vid 70 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 200 A över 70 m vid 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 5.46V (1.37%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 7.13V (1.78%)
Voltage at Load394.5 VLine Loss: 1892.2 W
Max Power & Breaker138.56 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A345.95 V (86.49%)54.1 V570.65 V (142.66%)119840.0 WDrop High
2.5 mm²24 A18 A207.57 V (51.89%)192.4 V342.39 V (85.6%)71904.0 WDrop High
4 mm²32 A25 A129.73 V (32.43%)270.3 V213.99 V (53.5%)44940.0 WDrop High
6 mm²41 A32 A86.49 V (21.62%)313.5 V142.66 V (35.67%)29960.0 WDrop High
10 mm²57 A44 A51.89 V (12.97%)348.1 V85.6 V (21.4%)17976.0 WDrop High
16 mm²76 A59 A32.43 V (8.11%)367.6 V53.5 V (13.37%)11235.0 WDrop High
25 mm²101 A78 A20.76 V (5.19%)379.2 V34.24 V (8.56%)7190.4 WDrop High
35 mm²125 A97 A14.83 V (3.71%)385.2 V24.46 V (6.11%)5136.0 WDrop High
50 mm²151 A118 A10.38 V (2.59%)389.6 V17.12 V (4.28%)3595.2 WDrop High
70 mm²192 A150 A7.41 V (1.85%)392.6 V12.23 V (3.06%)2568.0 WDrop High
95 mm²232 A181 A5.46 V (1.37%)394.5 V9.01 V (2.25%)1892.2 W✓ OK (≤3%)
120 mm²269 A210 A4.32 V (1.08%)395.7 V7.13 V (1.78%)1498.0 W✓ OK (≤3%)
150 mm²309 A241 A3.46 V (0.86%)396.5 V5.71 V (1.43%)1198.4 W✓ OK (≤3%)
185 mm²353 A275 A2.8 V (0.7%)397.2 V4.63 V (1.16%)971.7 W✓ OK (≤3%)
240 mm²415 A324 A2.16 V (0.54%)397.8 V3.57 V (0.89%)749.0 W✓ OK (≤3%)
300 mm²477 A372 A1.73 V (0.43%)398.3 V2.85 V (0.71%)599.2 W✓ OK (≤3%)
400 mm²570 A445 A1.3 V (0.32%)398.7 V2.14 V (0.53%)449.4 W✓ OK (≤3%)

FAQ — Kabelarea för 200 Ampere vid 70 Meter (400V)

Vilken kabelarea krävs för 200A vid 70 meter (400V)?

För 200 Ampere över 70 meter vid 400V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (5.46V / 1.37%).

Hur stor effekt motsvarar 200A vid 400V?

Det motsvarar 138.56 kW med en rekommenderad säkring på 200A.