Kabelarea för 700 Ampere vid 150 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 700 A över 150 m vid 230V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.62V (2.44%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 18.53V (8.06%)
Voltage at Load224.4 VLine Loss: 3932.2 W
Max Power & Breaker161.0 kW700A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 150m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2996.0 V (1302.61%) | 0.0 V | 4942.0 V (2148.7%) | 2097200.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1797.6 V (781.57%) | 0.0 V | 2965.2 V (1289.22%) | 1258320.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1123.5 V (488.48%) | 0.0 V | 1853.25 V (805.76%) | 786450.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 749.0 V (325.65%) | 0.0 V | 1235.5 V (537.17%) | 524300.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 449.4 V (195.39%) | 0.0 V | 741.3 V (322.3%) | 314580.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 280.88 V (122.12%) | 0.0 V | 463.31 V (201.44%) | 196612.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 179.76 V (78.16%) | 50.2 V | 296.52 V (128.92%) | 125832.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 128.4 V (55.83%) | 101.6 V | 211.8 V (92.09%) | 89880.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 89.88 V (39.08%) | 140.1 V | 148.26 V (64.46%) | 62916.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 64.2 V (27.91%) | 165.8 V | 105.9 V (46.04%) | 44940.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 47.31 V (20.57%) | 182.7 V | 78.03 V (33.93%) | 33113.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 37.45 V (16.28%) | 192.6 V | 61.77 V (26.86%) | 26215.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 29.96 V (13.03%) | 200.0 V | 49.42 V (21.49%) | 20972.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 24.29 V (10.56%) | 205.7 V | 40.07 V (17.42%) | 17004.3 W | Drop High |
| 240 mm² | 415 A | 324 A | 18.72 V (8.14%) | 211.3 V | 30.89 V (13.43%) | 13107.5 W | Drop High |
| 300 mm² | 477 A | 372 A | 14.98 V (6.51%) | 215.0 V | 24.71 V (10.74%) | 10486.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 11.23 V (4.88%) | 218.8 V | 18.53 V (8.06%) | 7864.5 W | Drop High |
FAQ — Kabelarea för 700 Ampere vid 150 Meter (230V)
Vilken kabelarea krävs för 700A vid 150 meter (230V)?
För 700 Ampere över 150 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.62V / 2.44%).
Hur stor effekt motsvarar 700A vid 230V?
Det motsvarar 161.0 kW med en rekommenderad säkring på 700A.
Related Lengths & Currents (230V)
700A · 5m (230V)700A · 10m (230V)700A · 15m (230V)700A · 20m (230V)700A · 25m (230V)700A · 30m (230V)700A · 35m (230V)700A · 40m (230V)700A · 45m (230V)700A · 50m (230V)700A · 60m (230V)700A · 70m (230V)10A · 150m (230V)16A · 150m (230V)20A · 150m (230V)25A · 150m (230V)32A · 150m (230V)40A · 150m (230V)50A · 150m (230V)63A · 150m (230V)80A · 150m (230V)100A · 150m (230V)125A · 150m (230V)160A · 150m (230V)200A · 150m (230V)