Kabelarea för 700 Ampere vid 20 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 700 A över 20 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.75V (0.33%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.47V (1.07%)
Voltage at Load229.2 VLine Loss: 524.3 W
Max Power & Breaker161.0 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A399.47 V (173.68%)0.0 V658.93 V (286.49%)279626.7 WDrop High
2.5 mm²24 A18 A239.68 V (104.21%)0.0 V395.36 V (171.9%)167776.0 WDrop High
4 mm²32 A25 A149.8 V (65.13%)80.2 V247.1 V (107.43%)104860.0 WDrop High
6 mm²41 A32 A99.87 V (43.42%)130.1 V164.73 V (71.62%)69906.7 WDrop High
10 mm²57 A44 A59.92 V (26.05%)170.1 V98.84 V (42.97%)41944.0 WDrop High
16 mm²76 A59 A37.45 V (16.28%)192.6 V61.77 V (26.86%)26215.0 WDrop High
25 mm²101 A78 A23.97 V (10.42%)206.0 V39.54 V (17.19%)16777.6 WDrop High
35 mm²125 A97 A17.12 V (7.44%)212.9 V28.24 V (12.28%)11984.0 WDrop High
50 mm²151 A118 A11.98 V (5.21%)218.0 V19.77 V (8.59%)8388.8 WDrop High
70 mm²192 A150 A8.56 V (3.72%)221.4 V14.12 V (6.14%)5992.0 WDrop High
95 mm²232 A181 A6.31 V (2.74%)223.7 V10.4 V (4.52%)4415.2 WDrop High
120 mm²269 A210 A4.99 V (2.17%)225.0 V8.24 V (3.58%)3495.3 WDrop High
150 mm²309 A241 A3.99 V (1.74%)226.0 V6.59 V (2.86%)2796.3 WDrop High
185 mm²353 A275 A3.24 V (1.41%)226.8 V5.34 V (2.32%)2267.2 WDrop High
240 mm²415 A324 A2.5 V (1.09%)227.5 V4.12 V (1.79%)1747.7 WDrop High
300 mm²477 A372 A2.0 V (0.87%)228.0 V3.29 V (1.43%)1398.1 WDrop High
400 mm²570 A445 A1.5 V (0.65%)228.5 V2.47 V (1.07%)1048.6 WDrop High

FAQ — Kabelarea för 700 Ampere vid 20 Meter (230V)

Vilken kabelarea krävs för 700A vid 20 meter (230V)?

För 700 Ampere över 20 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (0.75V / 0.33%).

Hur stor effekt motsvarar 700A vid 230V?

Det motsvarar 161.0 kW med en rekommenderad säkring på 700A.