Kabelarea för 750 Ampere vid 20 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 750 A över 20 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.69V (0.17%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.29V (0.57%)
Voltage at Load399.3 VLine Loss: 902.8 W
Max Power & Breaker519.62 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A370.66 V (92.66%)29.3 V611.41 V (152.85%)481500.0 WDrop High
2.5 mm²24 A18 A222.4 V (55.6%)177.6 V366.85 V (91.71%)288900.0 WDrop High
4 mm²32 A25 A139.0 V (34.75%)261.0 V229.28 V (57.32%)180562.5 WDrop High
6 mm²41 A32 A92.66 V (23.17%)307.3 V152.85 V (38.21%)120375.0 WDrop High
10 mm²57 A44 A55.6 V (13.9%)344.4 V91.71 V (22.93%)72225.0 WDrop High
16 mm²76 A59 A34.75 V (8.69%)365.3 V57.32 V (14.33%)45140.6 WDrop High
25 mm²101 A78 A22.24 V (5.56%)377.8 V36.68 V (9.17%)28890.0 WDrop High
35 mm²125 A97 A15.89 V (3.97%)384.1 V26.2 V (6.55%)20635.7 WDrop High
50 mm²151 A118 A11.12 V (2.78%)388.9 V18.34 V (4.59%)14445.0 WDrop High
70 mm²192 A150 A7.94 V (1.99%)392.1 V13.1 V (3.28%)10317.9 WDrop High
95 mm²232 A181 A5.85 V (1.46%)394.1 V9.65 V (2.41%)7602.6 WDrop High
120 mm²269 A210 A4.63 V (1.16%)395.4 V7.64 V (1.91%)6018.8 WDrop High
150 mm²309 A241 A3.71 V (0.93%)396.3 V6.11 V (1.53%)4815.0 WDrop High
185 mm²353 A275 A3.01 V (0.75%)397.0 V4.96 V (1.24%)3904.1 WDrop High
240 mm²415 A324 A2.32 V (0.58%)397.7 V3.82 V (0.96%)3009.4 WDrop High
300 mm²477 A372 A1.85 V (0.46%)398.1 V3.06 V (0.76%)2407.5 WDrop High
400 mm²570 A445 A1.39 V (0.35%)398.6 V2.29 V (0.57%)1805.6 WDrop High

FAQ — Kabelarea för 750 Ampere vid 20 Meter (400V)

Vilken kabelarea krävs för 750A vid 20 meter (400V)?

För 750 Ampere över 20 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (0.69V / 0.17%).

Hur stor effekt motsvarar 750A vid 400V?

Det motsvarar 519.62 kW med en rekommenderad säkring på 800A.