⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 160 Ampere vid 20 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 20 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 1.69V (0.42%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 2.06V (0.51%)
Voltage at Load398.3 VLine Loss: 469.6 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A79.07 V (19.77%)320.9 V130.43 V (32.61%)21913.6 WDrop High
2.5 mm²24 A18 A47.44 V (11.86%)352.6 V78.26 V (19.57%)13148.2 WDrop High
4 mm²32 A25 A29.65 V (7.41%)370.3 V48.91 V (12.23%)8217.6 WDrop High
6 mm²41 A32 A19.77 V (4.94%)380.2 V32.61 V (8.15%)5478.4 WDrop High
10 mm²57 A44 A11.86 V (2.97%)388.1 V19.57 V (4.89%)3287.0 WDrop High
16 mm²76 A59 A7.41 V (1.85%)392.6 V12.23 V (3.06%)2054.4 WDrop High
25 mm²101 A78 A4.74 V (1.19%)395.3 V7.83 V (1.96%)1314.8 WDrop High
35 mm²125 A97 A3.39 V (0.85%)396.6 V5.59 V (1.4%)939.2 WDrop High
50 mm²151 A118 A2.37 V (0.59%)397.6 V3.91 V (0.98%)657.4 WDrop High
70 mm²192 A150 A1.69 V (0.42%)398.3 V2.8 V (0.7%)469.6 W✓ OK (≤3%)
95 mm²232 A181 A1.25 V (0.31%)398.8 V2.06 V (0.51%)346.0 W✓ OK (≤3%)
120 mm²269 A210 A0.99 V (0.25%)399.0 V1.63 V (0.41%)273.9 W✓ OK (≤3%)
150 mm²309 A241 A0.79 V (0.2%)399.2 V1.3 V (0.33%)219.1 W✓ OK (≤3%)
185 mm²353 A275 A0.64 V (0.16%)399.4 V1.06 V (0.26%)177.7 W✓ OK (≤3%)
240 mm²415 A324 A0.49 V (0.12%)399.5 V0.82 V (0.2%)137.0 W✓ OK (≤3%)
300 mm²477 A372 A0.4 V (0.1%)399.6 V0.65 V (0.16%)109.6 W✓ OK (≤3%)
400 mm²570 A445 A0.3 V (0.07%)399.7 V0.49 V (0.12%)82.2 W✓ OK (≤3%)

FAQ — Kabelarea för 160 Ampere vid 20 Meter (400V)

Vilken kabelarea krävs för 160A vid 20 meter (400V)?

För 160 Ampere över 20 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (1.69V / 0.42%).

Hur stor effekt motsvarar 160A vid 400V?

Det motsvarar 110.85 kW med en rekommenderad säkring på 160A.