⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 80 Ampere vid 15 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 80 A över 15 m vid 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 1.78V (0.44%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 2.1V (0.52%)
Voltage at Load398.2 VLine Loss: 246.5 W
Max Power & Breaker55.43 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A29.65 V (7.41%)370.3 V48.91 V (12.23%)4108.8 WDrop High
2.5 mm²24 A18 A17.79 V (4.45%)382.2 V29.35 V (7.34%)2465.3 WDrop High
4 mm²32 A25 A11.12 V (2.78%)388.9 V18.34 V (4.59%)1540.8 WDrop High
6 mm²41 A32 A7.41 V (1.85%)392.6 V12.23 V (3.06%)1027.2 WDrop High
10 mm²57 A44 A4.45 V (1.11%)395.6 V7.34 V (1.83%)616.3 WDrop High
16 mm²76 A59 A2.78 V (0.69%)397.2 V4.59 V (1.15%)385.2 WDrop High
25 mm²101 A78 A1.78 V (0.44%)398.2 V2.93 V (0.73%)246.5 W✓ OK (≤3%)
35 mm²125 A97 A1.27 V (0.32%)398.7 V2.1 V (0.52%)176.1 W✓ OK (≤3%)
50 mm²151 A118 A0.89 V (0.22%)399.1 V1.47 V (0.37%)123.3 W✓ OK (≤3%)
70 mm²192 A150 A0.64 V (0.16%)399.4 V1.05 V (0.26%)88.0 W✓ OK (≤3%)
95 mm²232 A181 A0.47 V (0.12%)399.5 V0.77 V (0.19%)64.9 W✓ OK (≤3%)
120 mm²269 A210 A0.37 V (0.09%)399.6 V0.61 V (0.15%)51.4 W✓ OK (≤3%)
150 mm²309 A241 A0.3 V (0.07%)399.7 V0.49 V (0.12%)41.1 W✓ OK (≤3%)
185 mm²353 A275 A0.24 V (0.06%)399.8 V0.4 V (0.1%)33.3 W✓ OK (≤3%)
240 mm²415 A324 A0.19 V (0.05%)399.8 V0.31 V (0.08%)25.7 W✓ OK (≤3%)
300 mm²477 A372 A0.15 V (0.04%)399.9 V0.24 V (0.06%)20.5 W✓ OK (≤3%)
400 mm²570 A445 A0.11 V (0.03%)399.9 V0.18 V (0.05%)15.4 W✓ OK (≤3%)

FAQ — Kabelarea för 80 Ampere vid 15 Meter (400V)

Vilken kabelarea krävs för 80A vid 15 meter (400V)?

För 80 Ampere över 15 meter vid 400V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (1.78V / 0.44%).

Hur stor effekt motsvarar 80A vid 400V?

Det motsvarar 55.43 kW med en rekommenderad säkring på 80A.