Kabelarea för 125 Ampere vid 15 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 15 m vid 400V.
Copper Cable (≤3% Drop)35 mm²Drop: 1.99V (0.5%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 1.64V (0.41%)
Voltage at Load398.0 VLine Loss: 429.9 W
Max Power & Breaker86.6 kW125A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 15m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 46.33 V (11.58%) | 353.7 V | 76.43 V (19.11%) | 10031.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 27.8 V (6.95%) | 372.2 V | 45.86 V (11.46%) | 6018.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 17.37 V (4.34%) | 382.6 V | 28.66 V (7.17%) | 3761.7 W | Drop High |
| 6 mm² | 41 A | 32 A | 11.58 V (2.9%) | 388.4 V | 19.11 V (4.78%) | 2507.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 6.95 V (1.74%) | 393.1 V | 11.46 V (2.87%) | 1504.7 W | Drop High |
| 16 mm² | 76 A | 59 A | 4.34 V (1.09%) | 395.7 V | 7.17 V (1.79%) | 940.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 2.78 V (0.69%) | 397.2 V | 4.59 V (1.15%) | 601.9 W | Drop High |
| 35 mm² | 125 A | 97 A | 1.99 V (0.5%) | 398.0 V | 3.28 V (0.82%) | 429.9 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.39 V (0.35%) | 398.6 V | 2.29 V (0.57%) | 300.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.99 V (0.25%) | 399.0 V | 1.64 V (0.41%) | 215.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.73 V (0.18%) | 399.3 V | 1.21 V (0.3%) | 158.4 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.58 V (0.14%) | 399.4 V | 0.96 V (0.24%) | 125.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.46 V (0.12%) | 399.5 V | 0.76 V (0.19%) | 100.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.38 V (0.09%) | 399.6 V | 0.62 V (0.15%) | 81.3 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.29 V (0.07%) | 399.7 V | 0.48 V (0.12%) | 62.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.23 V (0.06%) | 399.8 V | 0.38 V (0.1%) | 50.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.17 V (0.04%) | 399.8 V | 0.29 V (0.07%) | 37.6 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 125 Ampere vid 15 Meter (400V)
Vilken kabelarea krävs för 125A vid 15 meter (400V)?
För 125 Ampere över 15 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (1.99V / 0.5%).
Hur stor effekt motsvarar 125A vid 400V?
Det motsvarar 86.6 kW med en rekommenderad säkring på 125A.
Related Lengths & Currents (400V)
125A · 5m (400V)125A · 10m (400V)125A · 20m (400V)125A · 25m (400V)125A · 30m (400V)125A · 35m (400V)125A · 40m (400V)125A · 45m (400V)125A · 50m (400V)125A · 60m (400V)125A · 70m (400V)10A · 15m (400V)16A · 15m (400V)20A · 15m (400V)25A · 15m (400V)32A · 15m (400V)40A · 15m (400V)50A · 15m (400V)63A · 15m (400V)80A · 15m (400V)100A · 15m (400V)160A · 15m (400V)200A · 15m (400V)