Kabelarea för 90 Ampere vid 45 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 90 A över 45 m vid 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 4.95V (2.15%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 5.72V (2.49%)
Voltage at Load225.0 VLine Loss: 445.7 W
Max Power & Breaker20.7 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A115.56 V (50.24%)114.4 V190.62 V (82.88%)10400.4 WDrop High
2.5 mm²24 A18 A69.34 V (30.15%)160.7 V114.37 V (49.73%)6240.2 WDrop High
4 mm²32 A25 A43.34 V (18.84%)186.7 V71.48 V (31.08%)3900.2 WDrop High
6 mm²41 A32 A28.89 V (12.56%)201.1 V47.65 V (20.72%)2600.1 WDrop High
10 mm²57 A44 A17.33 V (7.54%)212.7 V28.59 V (12.43%)1560.1 WDrop High
16 mm²76 A59 A10.83 V (4.71%)219.2 V17.87 V (7.77%)975.0 WDrop High
25 mm²101 A78 A6.93 V (3.01%)223.1 V11.44 V (4.97%)624.0 W~ ≤5%
35 mm²125 A97 A4.95 V (2.15%)225.0 V8.17 V (3.55%)445.7 W✓ OK (≤3%)
50 mm²151 A118 A3.47 V (1.51%)226.5 V5.72 V (2.49%)312.0 W✓ OK (≤3%)
70 mm²192 A150 A2.48 V (1.08%)227.5 V4.08 V (1.78%)222.9 W✓ OK (≤3%)
95 mm²232 A181 A1.82 V (0.79%)228.2 V3.01 V (1.31%)164.2 W✓ OK (≤3%)
120 mm²269 A210 A1.44 V (0.63%)228.6 V2.38 V (1.04%)130.0 W✓ OK (≤3%)
150 mm²309 A241 A1.16 V (0.5%)228.8 V1.91 V (0.83%)104.0 W✓ OK (≤3%)
185 mm²353 A275 A0.94 V (0.41%)229.1 V1.55 V (0.67%)84.3 W✓ OK (≤3%)
240 mm²415 A324 A0.72 V (0.31%)229.3 V1.19 V (0.52%)65.0 W✓ OK (≤3%)
300 mm²477 A372 A0.58 V (0.25%)229.4 V0.95 V (0.41%)52.0 W✓ OK (≤3%)
400 mm²570 A445 A0.43 V (0.19%)229.6 V0.71 V (0.31%)39.0 W✓ OK (≤3%)

FAQ — Kabelarea för 90 Ampere vid 45 Meter (230V)

Vilken kabelarea krävs för 90A vid 45 meter (230V)?

För 90 Ampere över 45 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (4.95V / 2.15%).

Hur stor effekt motsvarar 90A vid 230V?

Det motsvarar 20.7 kW med en rekommenderad säkring på 90A.