Kabelarea för 90 Ampere vid 60 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 90 A över 60 m vid 230V.
Copper Cable (≤3% Drop)35 mm²Drop: 6.6V (2.87%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.45V (2.37%)
Voltage at Load223.4 VLine Loss: 594.3 W
Max Power & Breaker20.7 kW90A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 60m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 154.08 V (66.99%) | 75.9 V | 254.16 V (110.5%) | 13867.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 92.45 V (40.19%) | 137.6 V | 152.5 V (66.3%) | 8320.3 W | Drop High |
| 4 mm² | 32 A | 25 A | 57.78 V (25.12%) | 172.2 V | 95.31 V (41.44%) | 5200.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 38.52 V (16.75%) | 191.5 V | 63.54 V (27.63%) | 3466.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 23.11 V (10.05%) | 206.9 V | 38.12 V (16.58%) | 2080.1 W | Drop High |
| 16 mm² | 76 A | 59 A | 14.45 V (6.28%) | 215.6 V | 23.83 V (10.36%) | 1300.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 9.24 V (4.02%) | 220.8 V | 15.25 V (6.63%) | 832.0 W | ~ ≤5% |
| 35 mm² | 125 A | 97 A | 6.6 V (2.87%) | 223.4 V | 10.89 V (4.74%) | 594.3 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 4.62 V (2.01%) | 225.4 V | 7.62 V (3.32%) | 416.0 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 3.3 V (1.44%) | 226.7 V | 5.45 V (2.37%) | 297.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 2.43 V (1.06%) | 227.6 V | 4.01 V (1.74%) | 219.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.93 V (0.84%) | 228.1 V | 3.18 V (1.38%) | 173.3 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.54 V (0.67%) | 228.5 V | 2.54 V (1.11%) | 138.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.25 V (0.54%) | 228.8 V | 2.06 V (0.9%) | 112.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.96 V (0.42%) | 229.0 V | 1.59 V (0.69%) | 86.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.77 V (0.33%) | 229.2 V | 1.27 V (0.55%) | 69.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.58 V (0.25%) | 229.4 V | 0.95 V (0.41%) | 52.0 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 90 Ampere vid 60 Meter (230V)
Vilken kabelarea krävs för 90A vid 60 meter (230V)?
För 90 Ampere över 60 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (6.6V / 2.87%).
Hur stor effekt motsvarar 90A vid 230V?
Det motsvarar 20.7 kW med en rekommenderad säkring på 90A.
Related Lengths & Currents (230V)
90A · 5m (230V)90A · 10m (230V)90A · 15m (230V)90A · 20m (230V)90A · 25m (230V)90A · 30m (230V)90A · 35m (230V)90A · 40m (230V)90A · 45m (230V)90A · 50m (230V)90A · 70m (230V)10A · 60m (230V)16A · 60m (230V)20A · 60m (230V)25A · 60m (230V)32A · 60m (230V)40A · 60m (230V)50A · 60m (230V)63A · 60m (230V)80A · 60m (230V)100A · 60m (230V)125A · 60m (230V)160A · 60m (230V)200A · 60m (230V)