⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 90 Ampere vid 60 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 90 A över 60 m vid 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 6.6V (2.87%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.45V (2.37%)
Voltage at Load223.4 VLine Loss: 594.3 W
Max Power & Breaker20.7 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A154.08 V (66.99%)75.9 V254.16 V (110.5%)13867.2 WDrop High
2.5 mm²24 A18 A92.45 V (40.19%)137.6 V152.5 V (66.3%)8320.3 WDrop High
4 mm²32 A25 A57.78 V (25.12%)172.2 V95.31 V (41.44%)5200.2 WDrop High
6 mm²41 A32 A38.52 V (16.75%)191.5 V63.54 V (27.63%)3466.8 WDrop High
10 mm²57 A44 A23.11 V (10.05%)206.9 V38.12 V (16.58%)2080.1 WDrop High
16 mm²76 A59 A14.45 V (6.28%)215.6 V23.83 V (10.36%)1300.0 WDrop High
25 mm²101 A78 A9.24 V (4.02%)220.8 V15.25 V (6.63%)832.0 W~ ≤5%
35 mm²125 A97 A6.6 V (2.87%)223.4 V10.89 V (4.74%)594.3 W✓ OK (≤3%)
50 mm²151 A118 A4.62 V (2.01%)225.4 V7.62 V (3.32%)416.0 W✓ OK (≤3%)
70 mm²192 A150 A3.3 V (1.44%)226.7 V5.45 V (2.37%)297.2 W✓ OK (≤3%)
95 mm²232 A181 A2.43 V (1.06%)227.6 V4.01 V (1.74%)219.0 W✓ OK (≤3%)
120 mm²269 A210 A1.93 V (0.84%)228.1 V3.18 V (1.38%)173.3 W✓ OK (≤3%)
150 mm²309 A241 A1.54 V (0.67%)228.5 V2.54 V (1.11%)138.7 W✓ OK (≤3%)
185 mm²353 A275 A1.25 V (0.54%)228.8 V2.06 V (0.9%)112.4 W✓ OK (≤3%)
240 mm²415 A324 A0.96 V (0.42%)229.0 V1.59 V (0.69%)86.7 W✓ OK (≤3%)
300 mm²477 A372 A0.77 V (0.33%)229.2 V1.27 V (0.55%)69.3 W✓ OK (≤3%)
400 mm²570 A445 A0.58 V (0.25%)229.4 V0.95 V (0.41%)52.0 W✓ OK (≤3%)

FAQ — Kabelarea för 90 Ampere vid 60 Meter (230V)

Vilken kabelarea krävs för 90A vid 60 meter (230V)?

För 90 Ampere över 60 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (6.6V / 2.87%).

Hur stor effekt motsvarar 90A vid 230V?

Det motsvarar 20.7 kW med en rekommenderad säkring på 90A.