Kabelarea för 900 Ampere vid 100 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 900 A över 100 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 4.17V (1.04%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 13.76V (3.44%)
Voltage at Load395.8 VLine Loss: 6500.2 W
Max Power & Breaker623.54 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2223.95 V (555.99%)0.0 V3668.48 V (917.12%)3466800.0 WDrop High
2.5 mm²24 A18 A1334.37 V (333.59%)0.0 V2201.09 V (550.27%)2080080.0 WDrop High
4 mm²32 A25 A833.98 V (208.5%)0.0 V1375.68 V (343.92%)1300050.0 WDrop High
6 mm²41 A32 A555.99 V (139.0%)0.0 V917.12 V (229.28%)866700.0 WDrop High
10 mm²57 A44 A333.59 V (83.4%)66.4 V550.27 V (137.57%)520020.0 WDrop High
16 mm²76 A59 A208.5 V (52.12%)191.5 V343.92 V (85.98%)325012.5 WDrop High
25 mm²101 A78 A133.44 V (33.36%)266.6 V220.11 V (55.03%)208008.0 WDrop High
35 mm²125 A97 A95.31 V (23.83%)304.7 V157.22 V (39.31%)148577.1 WDrop High
50 mm²151 A118 A66.72 V (16.68%)333.3 V110.05 V (27.51%)104004.0 WDrop High
70 mm²192 A150 A47.66 V (11.91%)352.3 V78.61 V (19.65%)74288.6 WDrop High
95 mm²232 A181 A35.12 V (8.78%)364.9 V57.92 V (14.48%)54738.9 WDrop High
120 mm²269 A210 A27.8 V (6.95%)372.2 V45.86 V (11.46%)43335.0 WDrop High
150 mm²309 A241 A22.24 V (5.56%)377.8 V36.68 V (9.17%)34668.0 WDrop High
185 mm²353 A275 A18.03 V (4.51%)382.0 V29.74 V (7.44%)28109.2 WDrop High
240 mm²415 A324 A13.9 V (3.47%)386.1 V22.93 V (5.73%)21667.5 WDrop High
300 mm²477 A372 A11.12 V (2.78%)388.9 V18.34 V (4.59%)17334.0 WDrop High
400 mm²570 A445 A8.34 V (2.08%)391.7 V13.76 V (3.44%)13000.5 WDrop High

FAQ — Kabelarea för 900 Ampere vid 100 Meter (400V)

Vilken kabelarea krävs för 900A vid 100 meter (400V)?

För 900 Ampere över 100 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (4.17V / 1.04%).

Hur stor effekt motsvarar 900A vid 400V?

Det motsvarar 623.54 kW med en rekommenderad säkring på 1000A.