Kabelarea för 900 Ampere vid 45 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 900 A över 45 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.17V (0.94%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.15V (3.11%)
Voltage at Load227.8 VLine Loss: 1950.1 W
Max Power & Breaker207.0 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1155.6 V (502.43%)0.0 V1906.2 V (828.78%)1040040.0 WDrop High
2.5 mm²24 A18 A693.36 V (301.46%)0.0 V1143.72 V (497.27%)624024.0 WDrop High
4 mm²32 A25 A433.35 V (188.41%)0.0 V714.82 V (310.79%)390015.0 WDrop High
6 mm²41 A32 A288.9 V (125.61%)0.0 V476.55 V (207.2%)260010.0 WDrop High
10 mm²57 A44 A173.34 V (75.37%)56.7 V285.93 V (124.32%)156006.0 WDrop High
16 mm²76 A59 A108.34 V (47.1%)121.7 V178.71 V (77.7%)97503.8 WDrop High
25 mm²101 A78 A69.34 V (30.15%)160.7 V114.37 V (49.73%)62402.4 WDrop High
35 mm²125 A97 A49.53 V (21.53%)180.5 V81.69 V (35.52%)44573.1 WDrop High
50 mm²151 A118 A34.67 V (15.07%)195.3 V57.19 V (24.86%)31201.2 WDrop High
70 mm²192 A150 A24.76 V (10.77%)205.2 V40.85 V (17.76%)22286.6 WDrop High
95 mm²232 A181 A18.25 V (7.93%)211.8 V30.1 V (13.09%)16421.7 WDrop High
120 mm²269 A210 A14.44 V (6.28%)215.6 V23.83 V (10.36%)13000.5 WDrop High
150 mm²309 A241 A11.56 V (5.02%)218.4 V19.06 V (8.29%)10400.4 WDrop High
185 mm²353 A275 A9.37 V (4.07%)220.6 V15.46 V (6.72%)8432.8 WDrop High
240 mm²415 A324 A7.22 V (3.14%)222.8 V11.91 V (5.18%)6500.2 WDrop High
300 mm²477 A372 A5.78 V (2.51%)224.2 V9.53 V (4.14%)5200.2 WDrop High
400 mm²570 A445 A4.33 V (1.88%)225.7 V7.15 V (3.11%)3900.2 WDrop High

FAQ — Kabelarea för 900 Ampere vid 45 Meter (230V)

Vilken kabelarea krävs för 900A vid 45 meter (230V)?

För 900 Ampere över 45 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (2.17V / 0.94%).

Hur stor effekt motsvarar 900A vid 230V?

Det motsvarar 207.0 kW med en rekommenderad säkring på 1000A.