⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 900 Ampere vid 30 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 900 A över 30 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.45V (0.63%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.77V (2.07%)
Voltage at Load228.6 VLine Loss: 1300.0 W
Max Power & Breaker207.0 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A770.4 V (334.96%)0.0 V1270.8 V (552.52%)693360.0 WDrop High
2.5 mm²24 A18 A462.24 V (200.97%)0.0 V762.48 V (331.51%)416016.0 WDrop High
4 mm²32 A25 A288.9 V (125.61%)0.0 V476.55 V (207.2%)260010.0 WDrop High
6 mm²41 A32 A192.6 V (83.74%)37.4 V317.7 V (138.13%)173340.0 WDrop High
10 mm²57 A44 A115.56 V (50.24%)114.4 V190.62 V (82.88%)104004.0 WDrop High
16 mm²76 A59 A72.23 V (31.4%)157.8 V119.14 V (51.8%)65002.5 WDrop High
25 mm²101 A78 A46.22 V (20.1%)183.8 V76.25 V (33.15%)41601.6 WDrop High
35 mm²125 A97 A33.02 V (14.36%)197.0 V54.46 V (23.68%)29715.4 WDrop High
50 mm²151 A118 A23.11 V (10.05%)206.9 V38.12 V (16.58%)20800.8 WDrop High
70 mm²192 A150 A16.51 V (7.18%)213.5 V27.23 V (11.84%)14857.7 WDrop High
95 mm²232 A181 A12.16 V (5.29%)217.8 V20.07 V (8.72%)10947.8 WDrop High
120 mm²269 A210 A9.63 V (4.19%)220.4 V15.88 V (6.91%)8667.0 WDrop High
150 mm²309 A241 A7.7 V (3.35%)222.3 V12.71 V (5.53%)6933.6 WDrop High
185 mm²353 A275 A6.25 V (2.72%)223.8 V10.3 V (4.48%)5621.8 WDrop High
240 mm²415 A324 A4.81 V (2.09%)225.2 V7.94 V (3.45%)4333.5 WDrop High
300 mm²477 A372 A3.85 V (1.67%)226.1 V6.35 V (2.76%)3466.8 WDrop High
400 mm²570 A445 A2.89 V (1.26%)227.1 V4.77 V (2.07%)2600.1 WDrop High

FAQ — Kabelarea för 900 Ampere vid 30 Meter (230V)

Vilken kabelarea krävs för 900A vid 30 meter (230V)?

För 900 Ampere över 30 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.45V / 0.63%).

Hur stor effekt motsvarar 900A vid 230V?

Det motsvarar 207.0 kW med en rekommenderad säkring på 1000A.