🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

100 Amp Wire Size at 1000 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)8× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.25V (35.39%)
Voltage at Load End11.7 VLoss: 0.32 V (32.2 W)
Power & Breaker (125%)1.2 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 1000 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A627.18 V (5226.54%)0.0 V1034.56 V (8621.35%)62718.5 WDrop/Amp High
12 AWG3.31 mm²20 A394.12 V (3284.35%)0.0 V650.12 V (5417.64%)39412.2 WDrop/Amp High
10 AWG5.26 mm²30 A248.01 V (2066.77%)0.0 V409.1 V (3409.2%)24801.2 WDrop/Amp High
8 AWG8.37 mm²50 A155.86 V (1298.83%)0.0 V257.1 V (2142.46%)15585.9 WDrop/Amp High
6 AWG13.3 mm²65 A98.09 V (817.38%)0.0 V161.8 V (1348.3%)9808.6 WDrop/Amp High
4 AWG21.15 mm²85 A61.68 V (514.0%)0.0 V101.74 V (847.87%)6168.1 WDrop/Amp High
3 AWG26.67 mm²100 A48.91 V (407.62%)0.0 V80.69 V (672.38%)4891.4 WDrop/Amp High
2 AWG33.62 mm²115 A38.8 V (323.36%)0.0 V64.01 V (533.38%)3880.3 WDrop/Amp High
1 AWG42.41 mm²130 A30.76 V (256.34%)0.0 V50.74 V (422.83%)3076.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A24.39 V (203.24%)0.0 V40.23 V (335.25%)2438.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A19.35 V (161.22%)0.0 V31.91 V (265.94%)1934.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.35 V (127.88%)0.0 V25.31 V (210.94%)1534.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.17 V (101.41%)0.0 V20.07 V (167.28%)1216.9 WDrop/Amp High
250 kcmil126.7 mm²255 A10.3 V (85.8%)1.7 V16.98 V (141.53%)1029.6 WDrop/Amp High
300 kcmil152.0 mm²285 A8.58 V (71.52%)3.4 V14.16 V (117.98%)858.3 WDrop/Amp High
350 kcmil177.3 mm²310 A7.36 V (61.32%)4.6 V12.14 V (101.14%)735.8 WDrop/Amp High
400 kcmil202.7 mm²335 A6.44 V (53.63%)5.6 V10.62 V (88.47%)643.6 WDrop/Amp High
500 kcmil253.4 mm²380 A5.15 V (42.9%)6.9 V8.49 V (70.77%)514.8 WDrop/Amp High
600 kcmil304.0 mm²420 A4.29 V (35.76%)7.7 V7.08 V (58.99%)429.1 WDrop/Amp High
750 kcmil380.0 mm²475 A3.43 V (28.61%)8.6 V5.66 V (47.19%)343.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.57 V (21.45%)9.4 V4.25 V (35.39%)257.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 1000 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 1000 feet one-way at 12V (DC), you need 8× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.32V (2.68%) and delivers 11.7V at the load.

What size aluminum wire is required for 100 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.25V (35.39%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.