100 Amp Wire Size at 150 Feet (12V DC (Solar / Automotive / Marine))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 150 ft (45.7 m) one-way run.
Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.61%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.64V (5.31%)
Voltage at Load End11.8 VLoss: 0.2 V (19.3 W)
Power & Breaker (125%)1.2 kW125A Breaker Recommended
All AWG & kcmil Wire Gauges for 100 Amps at 150 Feet (12V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 94.08 V (783.98%) | 0.0 V | 155.18 V (1293.2%) | 9407.8 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 59.12 V (492.65%) | 0.0 V | 97.52 V (812.65%) | 5911.8 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 37.2 V (310.02%) | 0.0 V | 61.37 V (511.38%) | 3720.2 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 23.38 V (194.82%) | 0.0 V | 38.56 V (321.37%) | 2337.9 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 14.71 V (122.61%) | 0.0 V | 24.27 V (202.25%) | 1471.3 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 9.25 V (77.1%) | 2.7 V | 15.26 V (127.18%) | 925.2 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 7.34 V (61.14%) | 4.7 V | 12.1 V (100.86%) | 733.7 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 5.82 V (48.5%) | 6.2 V | 9.6 V (80.01%) | 582.0 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 4.61 V (38.45%) | 7.4 V | 7.61 V (63.43%) | 461.4 W | Drop/Amp High |
| 1/0 AWG | 53.49 mm² | 150 A | 3.66 V (30.49%) | 8.3 V | 6.03 V (50.29%) | 365.8 W | Drop/Amp High |
| 2/0 AWG | 67.43 mm² | 175 A | 2.9 V (24.18%) | 9.1 V | 4.79 V (39.89%) | 290.2 W | Drop/Amp High |
| 3/0 AWG | 85.01 mm² | 200 A | 2.3 V (19.18%) | 9.7 V | 3.8 V (31.64%) | 230.2 W | Drop/Amp High |
| 4/0 AWG | 107.2 mm² | 230 A | 1.83 V (15.21%) | 10.2 V | 3.01 V (25.09%) | 182.5 W | Drop/Amp High |
| 250 kcmil | 126.7 mm² | 255 A | 1.54 V (12.87%) | 10.5 V | 2.55 V (21.23%) | 154.4 W | Drop/Amp High |
| 300 kcmil | 152.0 mm² | 285 A | 1.29 V (10.73%) | 10.7 V | 2.12 V (17.7%) | 128.7 W | Drop/Amp High |
| 350 kcmil | 177.3 mm² | 310 A | 1.1 V (9.2%) | 10.9 V | 1.82 V (15.17%) | 110.4 W | Drop/Amp High |
| 400 kcmil | 202.7 mm² | 335 A | 0.97 V (8.04%) | 11.0 V | 1.59 V (13.27%) | 96.5 W | Drop/Amp High |
| 500 kcmil | 253.4 mm² | 380 A | 0.77 V (6.44%) | 11.2 V | 1.27 V (10.62%) | 77.2 W | Drop/Amp High |
| 600 kcmil | 304.0 mm² | 420 A | 0.64 V (5.36%) | 11.4 V | 1.06 V (8.85%) | 64.4 W | Drop/Amp High |
| 750 kcmil | 380.0 mm² | 475 A | 0.51 V (4.29%) | 11.5 V | 0.85 V (7.08%) | 51.5 W | ~ ≤5% |
| 1000 kcmil | 506.7 mm² | 545 A | 0.39 V (3.22%) | 11.6 V | 0.64 V (5.31%) | 38.6 W | ~ ≤5% |
Frequently Asked Engineering Questions
What size copper wire do I need for 100 amps at 150 feet (12V)?
To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 150 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.2V (1.61%) and delivers 11.8V at the load.
What size aluminum wire is required for 100 amps at 150 feet?
Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.64V (5.31%).
What breaker size is needed for a 100A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.