150 Amp Wire Size at 150 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.42%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.96V (7.96%)
Voltage at Load End11.7 VLoss: 0.29 V (43.5 W)
Power & Breaker (125%)1.8 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 150 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A141.12 V (1175.97%)0.0 V232.78 V (1939.8%)21167.5 WDrop/Amp High
12 AWG3.31 mm²20 A88.68 V (738.98%)0.0 V146.28 V (1218.97%)13301.6 WDrop/Amp High
10 AWG5.26 mm²30 A55.8 V (465.02%)0.0 V92.05 V (767.07%)8370.4 WDrop/Amp High
8 AWG8.37 mm²50 A35.07 V (292.24%)0.0 V57.85 V (482.05%)5260.3 WDrop/Amp High
6 AWG13.3 mm²65 A22.07 V (183.91%)0.0 V36.4 V (303.37%)3310.4 WDrop/Amp High
4 AWG21.15 mm²85 A13.88 V (115.65%)0.0 V22.89 V (190.77%)2081.7 WDrop/Amp High
3 AWG26.67 mm²100 A11.01 V (91.71%)1.0 V18.15 V (151.29%)1650.9 WDrop/Amp High
2 AWG33.62 mm²115 A8.73 V (72.75%)3.3 V14.4 V (120.01%)1309.6 WDrop/Amp High
1 AWG42.41 mm²130 A6.92 V (57.68%)5.1 V11.42 V (95.14%)1038.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.49 V (45.73%)6.5 V9.05 V (75.43%)823.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.35 V (36.27%)7.6 V7.18 V (59.84%)652.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.45 V (28.77%)8.5 V5.7 V (47.46%)517.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.74 V (22.82%)9.3 V4.52 V (37.64%)410.7 WDrop/Amp High
250 kcmil126.7 mm²255 A2.32 V (19.31%)9.7 V3.82 V (31.85%)347.5 WDrop/Amp High
300 kcmil152.0 mm²285 A1.93 V (16.09%)10.1 V3.19 V (26.54%)289.7 WDrop/Amp High
350 kcmil177.3 mm²310 A1.66 V (13.8%)10.3 V2.73 V (22.76%)248.3 WDrop/Amp High
400 kcmil202.7 mm²335 A1.45 V (12.07%)10.6 V2.39 V (19.91%)217.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.16 V (9.65%)10.8 V1.91 V (15.92%)173.8 WDrop/Amp High
600 kcmil304.0 mm²420 A0.97 V (8.05%)11.0 V1.59 V (13.27%)144.8 WDrop/Amp High
750 kcmil380.0 mm²475 A0.77 V (6.44%)11.2 V1.27 V (10.62%)115.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.58 V (4.83%)11.4 V0.96 V (7.96%)86.9 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 150 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 150 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.29V (2.42%) and delivers 11.7V at the load.

What size aluminum wire is required for 150 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.96V (7.96%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.