⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 50 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 0.8%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 1.73V (0.83%)
Voltage at Load End206.3 VLoss: 1.66 V (360.5 W)
Power & Breaker (125%)45.03 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 50 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A33.95 V (16.32%)174.1 V56.0 V (26.92%)7349.8 WDrop/Amp High
12 AWG3.31 mm²20 A21.33 V (10.26%)186.7 V35.19 V (16.92%)4618.6 WDrop/Amp High
10 AWG5.26 mm²30 A13.42 V (6.45%)194.6 V22.14 V (10.65%)2906.4 WDrop/Amp High
8 AWG8.37 mm²50 A8.44 V (4.06%)199.6 V13.92 V (6.69%)1826.5 WDrop/Amp High
6 AWG13.3 mm²65 A5.31 V (2.55%)202.7 V8.76 V (4.21%)1149.4 WDrop/Amp High
4 AWG21.15 mm²85 A3.34 V (1.61%)204.7 V5.51 V (2.65%)722.8 WDrop/Amp High
3 AWG26.67 mm²100 A2.65 V (1.27%)205.4 V4.37 V (2.1%)573.2 WDrop/Amp High
2 AWG33.62 mm²115 A2.1 V (1.01%)205.9 V3.46 V (1.67%)454.7 WDrop/Amp High
1 AWG42.41 mm²130 A1.66 V (0.8%)206.3 V2.75 V (1.32%)360.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.32 V (0.63%)206.7 V2.18 V (1.05%)285.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.05 V (0.5%)207.0 V1.73 V (0.83%)226.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.83 V (0.4%)207.2 V1.37 V (0.66%)179.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.66 V (0.32%)207.3 V1.09 V (0.52%)142.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.56 V (0.27%)207.4 V0.92 V (0.44%)120.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.46 V (0.22%)207.5 V0.77 V (0.37%)100.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.4 V (0.19%)207.6 V0.66 V (0.32%)86.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.35 V (0.17%)207.7 V0.57 V (0.28%)75.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.28 V (0.13%)207.7 V0.46 V (0.22%)60.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.23 V (0.11%)207.8 V0.38 V (0.18%)50.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.19 V (0.09%)207.8 V0.31 V (0.15%)40.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (0.07%)207.9 V0.23 V (0.11%)30.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 50 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 50 feet one-way at 208V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 1.66V (0.8%) and delivers 206.3V at the load.

What size aluminum wire is required for 125 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 1.73V (0.83%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.