🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 150 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.92%
Aluminum Wire (≤3% Drop)4 AWGDrop: 2.29V (1.91%)
Voltage at Load End116.5 VLoss: 3.51 V (52.6 W)
Power & Breaker (125%)1.8 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 150 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A14.11 V (11.76%)105.9 V23.28 V (19.4%)211.7 WDrop/Amp High
12 AWG3.31 mm²20 A8.87 V (7.39%)111.1 V14.63 V (12.19%)133.0 WDrop/Amp High
10 AWG5.26 mm²30 A5.58 V (4.65%)114.4 V9.2 V (7.67%)83.7 W~ ≤5%
8 AWG8.37 mm²50 A3.51 V (2.92%)116.5 V5.78 V (4.82%)52.6 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.21 V (1.84%)117.8 V3.64 V (3.03%)33.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.39 V (1.16%)118.6 V2.29 V (1.91%)20.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.1 V (0.92%)118.9 V1.82 V (1.51%)16.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.87 V (0.73%)119.1 V1.44 V (1.2%)13.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.69 V (0.58%)119.3 V1.14 V (0.95%)10.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.55 V (0.46%)119.5 V0.91 V (0.75%)8.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.44 V (0.36%)119.6 V0.72 V (0.6%)6.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.35 V (0.29%)119.7 V0.57 V (0.47%)5.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.27 V (0.23%)119.7 V0.45 V (0.38%)4.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.23 V (0.19%)119.8 V0.38 V (0.32%)3.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.19 V (0.16%)119.8 V0.32 V (0.27%)2.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.17 V (0.14%)119.8 V0.27 V (0.23%)2.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.14 V (0.12%)119.9 V0.24 V (0.2%)2.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.12 V (0.1%)119.9 V0.19 V (0.16%)1.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.1 V (0.08%)119.9 V0.16 V (0.13%)1.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.08 V (0.06%)119.9 V0.13 V (0.11%)1.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.06 V (0.05%)119.9 V0.1 V (0.08%)0.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 150 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 150 feet one-way at 120V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 3.51V (2.92%) and delivers 116.5V at the load.

What size aluminum wire is required for 15 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 2.29V (1.91%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.