🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 75 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 2.33%
Aluminum Wire (≤3% Drop)8 AWGDrop: 2.89V (2.41%)
Voltage at Load End117.2 VLoss: 2.79 V (41.9 W)
Power & Breaker (125%)1.8 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 75 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A7.06 V (5.88%)112.9 V11.64 V (9.7%)105.8 WDrop/Amp High
12 AWG3.31 mm²20 A4.43 V (3.69%)115.6 V7.31 V (6.09%)66.5 W~ ≤5%
10 AWG5.26 mm²30 A2.79 V (2.33%)117.2 V4.6 V (3.84%)41.9 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A1.75 V (1.46%)118.2 V2.89 V (2.41%)26.3 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.1 V (0.92%)118.9 V1.82 V (1.52%)16.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.69 V (0.58%)119.3 V1.14 V (0.95%)10.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.55 V (0.46%)119.4 V0.91 V (0.76%)8.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.44 V (0.36%)119.6 V0.72 V (0.6%)6.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.35 V (0.29%)119.7 V0.57 V (0.48%)5.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.27 V (0.23%)119.7 V0.45 V (0.38%)4.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.22 V (0.18%)119.8 V0.36 V (0.3%)3.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.17 V (0.14%)119.8 V0.28 V (0.24%)2.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.14 V (0.11%)119.9 V0.23 V (0.19%)2.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.12 V (0.1%)119.9 V0.19 V (0.16%)1.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.1 V (0.08%)119.9 V0.16 V (0.13%)1.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.08 V (0.07%)119.9 V0.14 V (0.11%)1.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.07 V (0.06%)119.9 V0.12 V (0.1%)1.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.06 V (0.05%)119.9 V0.1 V (0.08%)0.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.05 V (0.04%)120.0 V0.08 V (0.07%)0.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.03%)120.0 V0.06 V (0.05%)0.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.02%)120.0 V0.05 V (0.04%)0.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 75 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 75 feet one-way at 120V (1-Phase), you need 10 AWG copper wire. This produces a voltage drop of 2.79V (2.33%) and delivers 117.2V at the load.

What size aluminum wire is required for 15 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 2.89V (2.41%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.