🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 30 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 0.46%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 1.14V (0.47%)
Voltage at Load End238.9 VLoss: 1.1 V (164.6 W)
Power & Breaker (125%)36.0 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A28.22 V (11.76%)211.8 V46.56 V (19.4%)4233.5 WDrop/Amp High
12 AWG3.31 mm²20 A17.74 V (7.39%)222.3 V29.26 V (12.19%)2660.3 WDrop/Amp High
10 AWG5.26 mm²30 A11.16 V (4.65%)228.8 V18.41 V (7.67%)1674.1 WDrop/Amp High
8 AWG8.37 mm²50 A7.01 V (2.92%)233.0 V11.57 V (4.82%)1052.1 WDrop/Amp High
6 AWG13.3 mm²65 A4.41 V (1.84%)235.6 V7.28 V (3.03%)662.1 WDrop/Amp High
4 AWG21.15 mm²85 A2.78 V (1.16%)237.2 V4.58 V (1.91%)416.3 WDrop/Amp High
3 AWG26.67 mm²100 A2.2 V (0.92%)237.8 V3.63 V (1.51%)330.2 WDrop/Amp High
2 AWG33.62 mm²115 A1.75 V (0.73%)238.3 V2.88 V (1.2%)261.9 WDrop/Amp High
1 AWG42.41 mm²130 A1.38 V (0.58%)238.6 V2.28 V (0.95%)207.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.1 V (0.46%)238.9 V1.81 V (0.75%)164.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.87 V (0.36%)239.1 V1.44 V (0.6%)130.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.69 V (0.29%)239.3 V1.14 V (0.47%)103.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.55 V (0.23%)239.5 V0.9 V (0.38%)82.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.46 V (0.19%)239.5 V0.76 V (0.32%)69.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.39 V (0.16%)239.6 V0.64 V (0.27%)57.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.33 V (0.14%)239.7 V0.55 V (0.23%)49.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.29 V (0.12%)239.7 V0.48 V (0.2%)43.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.23 V (0.1%)239.8 V0.38 V (0.16%)34.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.19 V (0.08%)239.8 V0.32 V (0.13%)29.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.15 V (0.06%)239.8 V0.25 V (0.11%)23.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.12 V (0.05%)239.9 V0.19 V (0.08%)17.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 30 feet one-way at 240V (1-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 1.1V (0.46%) and delivers 238.9V at the load.

What size aluminum wire is required for 150 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 1.14V (0.47%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.