🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 30 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 0.28%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 0.76V (0.32%)
Voltage at Load End239.3 VLoss: 0.66 V (198.7 W)
Power & Breaker (125%)72.0 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A56.45 V (23.52%)183.6 V93.11 V (38.8%)16934.0 WDrop/Amp High
12 AWG3.31 mm²20 A35.47 V (14.78%)204.5 V58.51 V (24.38%)10641.3 WDrop/Amp High
10 AWG5.26 mm²30 A22.32 V (9.3%)217.7 V36.82 V (15.34%)6696.3 WDrop/Amp High
8 AWG8.37 mm²50 A14.03 V (5.84%)226.0 V23.14 V (9.64%)4208.2 WDrop/Amp High
6 AWG13.3 mm²65 A8.83 V (3.68%)231.2 V14.56 V (6.07%)2648.3 WDrop/Amp High
4 AWG21.15 mm²85 A5.55 V (2.31%)234.4 V9.16 V (3.82%)1665.4 WDrop/Amp High
3 AWG26.67 mm²100 A4.4 V (1.83%)235.6 V7.26 V (3.03%)1320.7 WDrop/Amp High
2 AWG33.62 mm²115 A3.49 V (1.46%)236.5 V5.76 V (2.4%)1047.7 WDrop/Amp High
1 AWG42.41 mm²130 A2.77 V (1.15%)237.2 V4.57 V (1.9%)830.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.19 V (0.91%)237.8 V3.62 V (1.51%)658.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.74 V (0.73%)238.3 V2.87 V (1.2%)522.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.38 V (0.58%)238.6 V2.28 V (0.95%)414.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.1 V (0.46%)238.9 V1.81 V (0.75%)328.6 WDrop/Amp High
250 kcmil126.7 mm²255 A0.93 V (0.39%)239.1 V1.53 V (0.64%)278.0 WDrop/Amp High
300 kcmil152.0 mm²285 A0.77 V (0.32%)239.2 V1.27 V (0.53%)231.7 WDrop/Amp High
350 kcmil177.3 mm²310 A0.66 V (0.28%)239.3 V1.09 V (0.46%)198.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.58 V (0.24%)239.4 V0.96 V (0.4%)173.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.46 V (0.19%)239.5 V0.76 V (0.32%)139.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.39 V (0.16%)239.6 V0.64 V (0.27%)115.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.31 V (0.13%)239.7 V0.51 V (0.21%)92.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.23 V (0.1%)239.8 V0.38 V (0.16%)69.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 30 feet one-way at 240V (1-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 0.66V (0.28%) and delivers 239.3V at the load.

What size aluminum wire is required for 300 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 0.76V (0.32%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.