150 Amp Wire Size at 750 Feet (120V Single-Phase (US Standard Branch))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 750 ft (228.6 m) one-way run.
Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.78V (3.98%)
Voltage at Load End117.1 VLoss: 2.9 V (434.5 W)
Power & Breaker (125%)18.0 kW200A Breaker Recommended
All AWG & kcmil Wire Gauges for 150 Amps at 750 Feet (120V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 705.58 V (587.99%) | 0.0 V | 1163.88 V (969.9%) | 105837.4 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 443.39 V (369.49%) | 0.0 V | 731.38 V (609.48%) | 66508.1 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 279.01 V (232.51%) | 0.0 V | 460.24 V (383.54%) | 41852.1 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 175.34 V (146.12%) | 0.0 V | 289.23 V (241.03%) | 26301.3 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 110.35 V (91.96%) | 9.7 V | 182.02 V (151.68%) | 16552.0 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 69.39 V (57.83%) | 50.6 V | 114.46 V (95.39%) | 10408.6 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 55.03 V (45.86%) | 65.0 V | 90.77 V (75.64%) | 8254.3 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 43.65 V (36.38%) | 76.3 V | 72.01 V (60.01%) | 6547.9 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 34.61 V (28.84%) | 85.4 V | 57.08 V (47.57%) | 5190.8 W | Drop/Amp High |
| 1/0 AWG | 53.49 mm² | 150 A | 27.44 V (22.86%) | 92.6 V | 45.26 V (37.72%) | 4115.6 W | Drop/Amp High |
| 2/0 AWG | 67.43 mm² | 175 A | 21.76 V (18.14%) | 98.2 V | 35.9 V (29.92%) | 3264.7 W | Drop/Amp High |
| 3/0 AWG | 85.01 mm² | 200 A | 17.26 V (14.39%) | 102.7 V | 28.48 V (23.73%) | 2589.6 W | Drop/Amp High |
| 4/0 AWG | 107.2 mm² | 230 A | 13.69 V (11.41%) | 106.3 V | 22.58 V (18.82%) | 2053.6 W | Drop/Amp High |
| 250 kcmil | 126.7 mm² | 255 A | 11.58 V (9.65%) | 108.4 V | 19.11 V (15.92%) | 1737.5 W | Drop/Amp High |
| 300 kcmil | 152.0 mm² | 285 A | 9.66 V (8.05%) | 110.3 V | 15.93 V (13.27%) | 1448.3 W | Drop/Amp High |
| 350 kcmil | 177.3 mm² | 310 A | 8.28 V (6.9%) | 111.7 V | 13.65 V (11.38%) | 1241.6 W | Drop/Amp High |
| 400 kcmil | 202.7 mm² | 335 A | 7.24 V (6.03%) | 112.8 V | 11.94 V (9.95%) | 1086.0 W | Drop/Amp High |
| 500 kcmil | 253.4 mm² | 380 A | 5.79 V (4.83%) | 114.2 V | 9.55 V (7.96%) | 868.8 W | ~ ≤5% |
| 600 kcmil | 304.0 mm² | 420 A | 4.83 V (4.02%) | 115.2 V | 7.96 V (6.64%) | 724.2 W | ~ ≤5% |
| 750 kcmil | 380.0 mm² | 475 A | 3.86 V (3.22%) | 116.1 V | 6.37 V (5.31%) | 579.3 W | ~ ≤5% |
| 1000 kcmil | 506.7 mm² | 545 A | 2.9 V (2.41%) | 117.1 V | 4.78 V (3.98%) | 434.5 W | ✓ PASS (≤3%) |
Frequently Asked Engineering Questions
What size copper wire do I need for 150 amps at 750 feet (120V)?
To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 750 feet one-way at 120V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 2.9V (2.41%) and delivers 117.1V at the load.
What size aluminum wire is required for 150 amps at 750 feet?
Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.78V (3.98%).
What breaker size is needed for a 150A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.