🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 125 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.4%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 3.18V (2.65%)
Voltage at Load End117.1 VLoss: 2.88 V (431.6 W)
Power & Breaker (125%)18.0 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 125 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A117.6 V (98.0%)2.4 V193.98 V (161.65%)17639.6 WDrop/Amp High
12 AWG3.31 mm²20 A73.9 V (61.58%)46.1 V121.9 V (101.58%)11084.7 WDrop/Amp High
10 AWG5.26 mm²30 A46.5 V (38.75%)73.5 V76.71 V (63.92%)6975.3 WDrop/Amp High
8 AWG8.37 mm²50 A29.22 V (24.35%)90.8 V48.21 V (40.17%)4383.5 WDrop/Amp High
6 AWG13.3 mm²65 A18.39 V (15.33%)101.6 V30.34 V (25.28%)2758.7 WDrop/Amp High
4 AWG21.15 mm²85 A11.57 V (9.64%)108.4 V19.08 V (15.9%)1734.8 WDrop/Amp High
3 AWG26.67 mm²100 A9.17 V (7.64%)110.8 V15.13 V (12.61%)1375.7 WDrop/Amp High
2 AWG33.62 mm²115 A7.28 V (6.06%)112.7 V12.0 V (10.0%)1091.3 WDrop/Amp High
1 AWG42.41 mm²130 A5.77 V (4.81%)114.2 V9.51 V (7.93%)865.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.57 V (3.81%)115.4 V7.54 V (6.29%)685.9 W~ ≤5%
2/0 AWG67.43 mm²175 A3.63 V (3.02%)116.4 V5.98 V (4.99%)544.1 W~ ≤5%
3/0 AWG85.01 mm²200 A2.88 V (2.4%)117.1 V4.75 V (3.96%)431.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.28 V (1.9%)117.7 V3.76 V (3.14%)342.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.93 V (1.61%)118.1 V3.18 V (2.65%)289.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.61 V (1.34%)118.4 V2.65 V (2.21%)241.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.38 V (1.15%)118.6 V2.28 V (1.9%)206.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.21 V (1.01%)118.8 V1.99 V (1.66%)181.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.97 V (0.8%)119.0 V1.59 V (1.33%)144.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.8 V (0.67%)119.2 V1.33 V (1.11%)120.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.64 V (0.54%)119.4 V1.06 V (0.88%)96.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.48 V (0.4%)119.5 V0.8 V (0.66%)72.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 125 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 125 feet one-way at 120V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 2.88V (2.4%) and delivers 117.1V at the load.

What size aluminum wire is required for 150 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 3.18V (2.65%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.