🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 175 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.97%
Aluminum Wire (≤3% Drop)6 AWGDrop: 4.9V (2.04%)
Voltage at Load End235.3 VLoss: 4.72 V (163.7 W)
Power & Breaker (125%)8.31 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A19.01 V (7.92%)221.0 V31.36 V (13.07%)658.5 WDrop/Amp High
12 AWG3.31 mm²20 A11.95 V (4.98%)228.1 V19.71 V (8.21%)413.8 W~ ≤5%
10 AWG5.26 mm²30 A7.52 V (3.13%)232.5 V12.4 V (5.17%)260.4 W~ ≤5%
8 AWG8.37 mm²50 A4.72 V (1.97%)235.3 V7.79 V (3.25%)163.7 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.97 V (1.24%)237.0 V4.9 V (2.04%)103.0 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.87 V (0.78%)238.1 V3.08 V (1.28%)64.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.48 V (0.62%)238.5 V2.45 V (1.02%)51.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.18 V (0.49%)238.8 V1.94 V (0.81%)40.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.93 V (0.39%)239.1 V1.54 V (0.64%)32.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.74 V (0.31%)239.3 V1.22 V (0.51%)25.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.59 V (0.24%)239.4 V0.97 V (0.4%)20.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.47 V (0.19%)239.5 V0.77 V (0.32%)16.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.37 V (0.15%)239.6 V0.61 V (0.25%)12.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.31 V (0.13%)239.7 V0.51 V (0.21%)10.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.26 V (0.11%)239.7 V0.43 V (0.18%)9.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.22 V (0.09%)239.8 V0.37 V (0.15%)7.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.2 V (0.08%)239.8 V0.32 V (0.13%)6.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.16 V (0.07%)239.8 V0.26 V (0.11%)5.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.13 V (0.05%)239.9 V0.21 V (0.09%)4.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.04%)239.9 V0.17 V (0.07%)3.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.03%)239.9 V0.13 V (0.05%)2.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 175 feet one-way at 240V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 4.72V (1.97%) and delivers 235.3V at the load.

What size aluminum wire is required for 20 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 4.9V (2.04%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.