⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

200 Amp Wire Size at 120 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 0.66%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 3.53V (0.74%)
Voltage at Load End476.8 VLoss: 3.19 V (1104.9 W)
Power & Breaker (125%)166.28 kW250A Breaker Recommended

All AWG & kcmil Wire Gauges for 200 Amps at 120 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A130.36 V (27.16%)349.6 V215.03 V (44.8%)45157.3 WDrop/Amp High
12 AWG3.31 mm²20 A81.92 V (17.07%)398.1 V135.12 V (28.15%)28376.8 WDrop/Amp High
10 AWG5.26 mm²30 A51.55 V (10.74%)428.5 V85.03 V (17.71%)17856.9 WDrop/Amp High
8 AWG8.37 mm²50 A32.39 V (6.75%)447.6 V53.44 V (11.13%)11221.9 WDrop/Amp High
6 AWG13.3 mm²65 A20.39 V (4.25%)459.6 V33.63 V (7.01%)7062.2 WDrop/Amp High
4 AWG21.15 mm²85 A12.82 V (2.67%)467.2 V21.15 V (4.41%)4441.0 WDrop/Amp High
3 AWG26.67 mm²100 A10.17 V (2.12%)469.8 V16.77 V (3.49%)3521.8 WDrop/Amp High
2 AWG33.62 mm²115 A8.06 V (1.68%)471.9 V13.3 V (2.77%)2793.8 WDrop/Amp High
1 AWG42.41 mm²130 A6.39 V (1.33%)473.6 V10.55 V (2.2%)2214.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.07 V (1.06%)474.9 V8.36 V (1.74%)1756.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.02 V (0.84%)476.0 V6.63 V (1.38%)1393.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.19 V (0.66%)476.8 V5.26 V (1.1%)1104.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.53 V (0.53%)477.5 V4.17 V (0.87%)876.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.14 V (0.45%)477.9 V3.53 V (0.74%)741.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.78 V (0.37%)478.2 V2.94 V (0.61%)617.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.53 V (0.32%)478.5 V2.52 V (0.53%)529.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.34 V (0.28%)478.7 V2.21 V (0.46%)463.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.07 V (0.22%)478.9 V1.77 V (0.37%)370.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.89 V (0.19%)479.1 V1.47 V (0.31%)309.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.71 V (0.15%)479.3 V1.18 V (0.25%)247.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.54 V (0.11%)479.5 V0.88 V (0.18%)185.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 200 amps at 120 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 120 feet one-way at 480V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 3.19V (0.66%) and delivers 476.8V at the load.

What size aluminum wire is required for 200 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 3.53V (0.74%).

What breaker size is needed for a 200A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.