🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 120 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 0.83%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 4.15V (0.86%)
Voltage at Load End476.0 VLoss: 4.0 V (865.1 W)
Power & Breaker (125%)103.92 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 120 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A81.47 V (16.97%)398.5 V134.39 V (28.0%)17639.6 WDrop/Amp High
12 AWG3.31 mm²20 A51.2 V (10.67%)428.8 V84.45 V (17.59%)11084.7 WDrop/Amp High
10 AWG5.26 mm²30 A32.22 V (6.71%)447.8 V53.14 V (11.07%)6975.3 WDrop/Amp High
8 AWG8.37 mm²50 A20.25 V (4.22%)459.8 V33.4 V (6.96%)4383.5 WDrop/Amp High
6 AWG13.3 mm²65 A12.74 V (2.65%)467.3 V21.02 V (4.38%)2758.7 WDrop/Amp High
4 AWG21.15 mm²85 A8.01 V (1.67%)472.0 V13.22 V (2.75%)1734.8 WDrop/Amp High
3 AWG26.67 mm²100 A6.35 V (1.32%)473.6 V10.48 V (2.18%)1375.7 WDrop/Amp High
2 AWG33.62 mm²115 A5.04 V (1.05%)475.0 V8.31 V (1.73%)1091.3 WDrop/Amp High
1 AWG42.41 mm²130 A4.0 V (0.83%)476.0 V6.59 V (1.37%)865.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.17 V (0.66%)476.8 V5.23 V (1.09%)685.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.51 V (0.52%)477.5 V4.15 V (0.86%)544.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.99 V (0.42%)478.0 V3.29 V (0.69%)431.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.58 V (0.33%)478.4 V2.61 V (0.54%)342.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.34 V (0.28%)478.7 V2.21 V (0.46%)289.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.11 V (0.23%)478.9 V1.84 V (0.38%)241.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.96 V (0.2%)479.0 V1.58 V (0.33%)206.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.84 V (0.17%)479.2 V1.38 V (0.29%)181.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.67 V (0.14%)479.3 V1.1 V (0.23%)144.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.56 V (0.12%)479.4 V0.92 V (0.19%)120.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.45 V (0.09%)479.6 V0.74 V (0.15%)96.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.33 V (0.07%)479.7 V0.55 V (0.11%)72.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 120 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 120 feet one-way at 480V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 4.0V (0.83%) and delivers 476.0V at the load.

What size aluminum wire is required for 125 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 4.15V (0.86%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.