⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 125 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.03%
Aluminum Wire (≤3% Drop)6 AWGDrop: 4.38V (2.11%)
Voltage at Load End203.8 VLoss: 4.22 V (182.6 W)
Power & Breaker (125%)9.01 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 125 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A16.97 V (8.16%)191.0 V28.0 V (13.46%)735.0 WDrop/Amp High
12 AWG3.31 mm²20 A10.67 V (5.13%)197.3 V17.59 V (8.46%)461.9 WDrop/Amp High
10 AWG5.26 mm²30 A6.71 V (3.23%)201.3 V11.07 V (5.32%)290.6 W~ ≤5%
8 AWG8.37 mm²50 A4.22 V (2.03%)203.8 V6.96 V (3.35%)182.6 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.65 V (1.28%)205.3 V4.38 V (2.11%)114.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.67 V (0.8%)206.3 V2.75 V (1.32%)72.3 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.32 V (0.64%)206.7 V2.18 V (1.05%)57.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.05 V (0.5%)206.9 V1.73 V (0.83%)45.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.83 V (0.4%)207.2 V1.37 V (0.66%)36.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.66 V (0.32%)207.3 V1.09 V (0.52%)28.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.52 V (0.25%)207.5 V0.86 V (0.42%)22.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.42 V (0.2%)207.6 V0.69 V (0.33%)18.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.33 V (0.16%)207.7 V0.54 V (0.26%)14.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.28 V (0.13%)207.7 V0.46 V (0.22%)12.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.23 V (0.11%)207.8 V0.38 V (0.18%)10.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.2 V (0.1%)207.8 V0.33 V (0.16%)8.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.17 V (0.08%)207.8 V0.29 V (0.14%)7.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.14 V (0.07%)207.9 V0.23 V (0.11%)6.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.12 V (0.06%)207.9 V0.19 V (0.09%)5.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.09 V (0.04%)207.9 V0.15 V (0.07%)4.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.07 V (0.03%)207.9 V0.11 V (0.06%)3.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 125 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 125 feet one-way at 208V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 4.22V (2.03%) and delivers 203.8V at the load.

What size aluminum wire is required for 25 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 4.38V (2.11%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.