⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 125 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 1.15%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 2.76V (1.33%)
Voltage at Load End205.6 VLoss: 2.39 V (1241.6 W)
Power & Breaker (125%)108.08 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 125 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A203.68 V (97.93%)4.3 V335.98 V (161.53%)105837.4 WDrop/Amp High
12 AWG3.31 mm²20 A127.99 V (61.54%)80.0 V211.13 V (101.51%)66508.1 WDrop/Amp High
10 AWG5.26 mm²30 A80.54 V (38.72%)127.5 V132.86 V (63.88%)41852.1 WDrop/Amp High
8 AWG8.37 mm²50 A50.62 V (24.34%)157.4 V83.49 V (40.14%)26301.3 WDrop/Amp High
6 AWG13.3 mm²65 A31.85 V (15.31%)176.1 V52.54 V (25.26%)16552.0 WDrop/Amp High
4 AWG21.15 mm²85 A20.03 V (9.63%)188.0 V33.04 V (15.89%)10408.6 WDrop/Amp High
3 AWG26.67 mm²100 A15.89 V (7.64%)192.1 V26.2 V (12.6%)8254.3 WDrop/Amp High
2 AWG33.62 mm²115 A12.6 V (6.06%)195.4 V20.79 V (9.99%)6547.9 WDrop/Amp High
1 AWG42.41 mm²130 A9.99 V (4.8%)198.0 V16.48 V (7.92%)5190.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.92 V (3.81%)200.1 V13.06 V (6.28%)4115.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.28 V (3.02%)201.7 V10.36 V (4.98%)3264.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.98 V (2.4%)203.0 V8.22 V (3.95%)2589.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.95 V (1.9%)204.0 V6.52 V (3.13%)2053.6 WDrop/Amp High
250 kcmil126.7 mm²255 A3.34 V (1.61%)204.7 V5.52 V (2.65%)1737.5 WDrop/Amp High
300 kcmil152.0 mm²285 A2.79 V (1.34%)205.2 V4.6 V (2.21%)1448.3 WDrop/Amp High
350 kcmil177.3 mm²310 A2.39 V (1.15%)205.6 V3.94 V (1.9%)1241.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.09 V (1.0%)205.9 V3.45 V (1.66%)1086.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.67 V (0.8%)206.3 V2.76 V (1.33%)868.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.39 V (0.67%)206.6 V2.3 V (1.11%)724.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.11 V (0.54%)206.9 V1.84 V (0.88%)579.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.84 V (0.4%)207.2 V1.38 V (0.66%)434.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 125 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 125 feet one-way at 208V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 2.39V (1.15%) and delivers 205.6V at the load.

What size aluminum wire is required for 300 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 2.76V (1.33%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.