⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 125 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 1.06%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 2.53V (1.05%)
Voltage at Load End237.4 VLoss: 2.55 V (1217.0 W)
Power & Breaker (125%)114.32 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A186.71 V (77.8%)53.3 V307.99 V (128.33%)88932.8 WDrop/Amp High
12 AWG3.31 mm²20 A117.33 V (48.89%)122.7 V193.54 V (80.64%)55885.3 WDrop/Amp High
10 AWG5.26 mm²30 A73.83 V (30.76%)166.2 V121.79 V (50.75%)35167.4 WDrop/Amp High
8 AWG8.37 mm²50 A46.4 V (19.33%)193.6 V76.54 V (31.89%)22100.4 WDrop/Amp High
6 AWG13.3 mm²65 A29.2 V (12.17%)210.8 V48.17 V (20.07%)13908.3 WDrop/Amp High
4 AWG21.15 mm²85 A18.36 V (7.65%)221.6 V30.29 V (12.62%)8746.1 WDrop/Amp High
3 AWG26.67 mm²100 A14.56 V (6.07%)225.4 V24.02 V (10.01%)6935.9 WDrop/Amp High
2 AWG33.62 mm²115 A11.55 V (4.81%)228.4 V19.05 V (7.94%)5502.1 WDrop/Amp High
1 AWG42.41 mm²130 A9.16 V (3.82%)230.8 V15.11 V (6.29%)4361.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.26 V (3.03%)232.7 V11.98 V (4.99%)3458.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.76 V (2.4%)234.2 V9.5 V (3.96%)2743.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.57 V (1.9%)235.4 V7.54 V (3.14%)2176.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.62 V (1.51%)236.4 V5.98 V (2.49%)1725.6 WDrop/Amp High
250 kcmil126.7 mm²255 A3.07 V (1.28%)236.9 V5.06 V (2.11%)1460.0 WDrop/Amp High
300 kcmil152.0 mm²285 A2.55 V (1.06%)237.4 V4.21 V (1.76%)1217.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.19 V (0.91%)237.8 V3.61 V (1.51%)1043.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.92 V (0.8%)238.1 V3.16 V (1.32%)912.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.53 V (0.64%)238.5 V2.53 V (1.05%)730.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.28 V (0.53%)238.7 V2.11 V (0.88%)608.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.02 V (0.43%)239.0 V1.69 V (0.7%)486.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.77 V (0.32%)239.2 V1.26 V (0.53%)365.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 125 feet one-way at 240V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 2.55V (1.06%) and delivers 237.4V at the load.

What size aluminum wire is required for 275 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 2.53V (1.05%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.