🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 175 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 1.49%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 3.54V (1.47%)
Voltage at Load End236.4 VLoss: 3.58 V (1703.8 W)
Power & Breaker (125%)114.32 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A261.39 V (108.91%)0.0 V431.18 V (179.66%)124505.9 WDrop/Amp High
12 AWG3.31 mm²20 A164.26 V (68.44%)75.7 V270.95 V (112.9%)78239.4 WDrop/Amp High
10 AWG5.26 mm²30 A103.37 V (43.07%)136.6 V170.5 V (71.04%)49234.3 WDrop/Amp High
8 AWG8.37 mm²50 A64.96 V (27.07%)175.0 V107.15 V (44.65%)30940.5 WDrop/Amp High
6 AWG13.3 mm²65 A40.88 V (17.03%)199.1 V67.43 V (28.1%)19471.6 WDrop/Amp High
4 AWG21.15 mm²85 A25.71 V (10.71%)214.3 V42.4 V (17.67%)12244.6 WDrop/Amp High
3 AWG26.67 mm²100 A20.39 V (8.49%)219.6 V33.63 V (14.01%)9710.2 WDrop/Amp High
2 AWG33.62 mm²115 A16.17 V (6.74%)223.8 V26.68 V (11.12%)7702.9 WDrop/Amp High
1 AWG42.41 mm²130 A12.82 V (5.34%)227.2 V21.15 V (8.81%)6106.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.16 V (4.24%)229.8 V16.77 V (6.99%)4841.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.06 V (3.36%)231.9 V13.3 V (5.54%)3840.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.4 V (2.66%)233.6 V10.55 V (4.4%)3046.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.07 V (2.11%)234.9 V8.37 V (3.49%)2415.8 WDrop/Amp High
250 kcmil126.7 mm²255 A4.29 V (1.79%)235.7 V7.08 V (2.95%)2044.0 WDrop/Amp High
300 kcmil152.0 mm²285 A3.58 V (1.49%)236.4 V5.9 V (2.46%)1703.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.07 V (1.28%)236.9 V5.06 V (2.11%)1460.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.68 V (1.12%)237.3 V4.42 V (1.84%)1277.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.15 V (0.89%)237.9 V3.54 V (1.47%)1022.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.79 V (0.75%)238.2 V2.95 V (1.23%)851.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.43 V (0.6%)238.6 V2.36 V (0.98%)681.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.07 V (0.45%)238.9 V1.77 V (0.74%)511.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 175 feet one-way at 240V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 3.58V (1.49%) and delivers 236.4V at the load.

What size aluminum wire is required for 275 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 3.54V (1.47%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.