⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 150 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 1.48%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 3.5V (1.46%)
Voltage at Load End236.5 VLoss: 3.54 V (973.6 W)
Power & Breaker (125%)66.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A258.71 V (107.8%)0.0 V426.76 V (177.82%)71146.3 WDrop/Amp High
12 AWG3.31 mm²20 A162.58 V (67.74%)77.4 V268.17 V (111.74%)44708.2 WDrop/Amp High
10 AWG5.26 mm²30 A102.31 V (42.63%)137.7 V168.76 V (70.31%)28133.9 WDrop/Amp High
8 AWG8.37 mm²50 A64.29 V (26.79%)175.7 V106.05 V (44.19%)17680.3 WDrop/Amp High
6 AWG13.3 mm²65 A40.46 V (16.86%)199.5 V66.74 V (27.81%)11126.6 WDrop/Amp High
4 AWG21.15 mm²85 A25.44 V (10.6%)214.6 V41.97 V (17.49%)6996.9 WDrop/Amp High
3 AWG26.67 mm²100 A20.18 V (8.41%)219.8 V33.28 V (13.87%)5548.7 WDrop/Amp High
2 AWG33.62 mm²115 A16.01 V (6.67%)224.0 V26.4 V (11.0%)4401.7 WDrop/Amp High
1 AWG42.41 mm²130 A12.69 V (5.29%)227.3 V20.93 V (8.72%)3489.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.06 V (4.19%)229.9 V16.59 V (6.91%)2766.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.98 V (3.33%)232.0 V13.16 V (5.49%)2194.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.33 V (2.64%)233.7 V10.44 V (4.35%)1740.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.02 V (2.09%)235.0 V8.28 V (3.45%)1380.4 WDrop/Amp High
250 kcmil126.7 mm²255 A4.25 V (1.77%)235.8 V7.01 V (2.92%)1168.0 WDrop/Amp High
300 kcmil152.0 mm²285 A3.54 V (1.48%)236.5 V5.84 V (2.43%)973.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.04 V (1.26%)237.0 V5.01 V (2.09%)834.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.65 V (1.11%)237.3 V4.38 V (1.82%)730.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.12 V (0.88%)237.9 V3.5 V (1.46%)584.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.77 V (0.74%)238.2 V2.92 V (1.22%)486.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.42 V (0.59%)238.6 V2.34 V (0.97%)389.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.06 V (0.44%)238.9 V1.75 V (0.73%)292.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 150 feet one-way at 240V (1-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 3.54V (1.48%) and delivers 236.5V at the load.

What size aluminum wire is required for 275 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 3.5V (1.46%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.