⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 125 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 1.23%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 2.92V (1.22%)
Voltage at Load End237.0 VLoss: 2.95 V (811.3 W)
Power & Breaker (125%)66.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A215.59 V (89.83%)24.4 V355.63 V (148.18%)59288.5 WDrop/Amp High
12 AWG3.31 mm²20 A135.48 V (56.45%)104.5 V223.48 V (93.12%)37256.9 WDrop/Amp High
10 AWG5.26 mm²30 A85.25 V (35.52%)154.7 V140.63 V (58.6%)23444.9 WDrop/Amp High
8 AWG8.37 mm²50 A53.58 V (22.32%)186.4 V88.38 V (36.82%)14733.6 WDrop/Amp High
6 AWG13.3 mm²65 A33.72 V (14.05%)206.3 V55.62 V (23.17%)9272.2 WDrop/Amp High
4 AWG21.15 mm²85 A21.2 V (8.83%)218.8 V34.97 V (14.57%)5830.7 WDrop/Amp High
3 AWG26.67 mm²100 A16.81 V (7.01%)223.2 V27.74 V (11.56%)4623.9 WDrop/Amp High
2 AWG33.62 mm²115 A13.34 V (5.56%)226.7 V22.0 V (9.17%)3668.1 WDrop/Amp High
1 AWG42.41 mm²130 A10.57 V (4.41%)229.4 V17.44 V (7.27%)2907.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.38 V (3.49%)231.6 V13.83 V (5.76%)2305.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.65 V (2.77%)233.3 V10.97 V (4.57%)1828.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.28 V (2.2%)234.7 V8.7 V (3.63%)1450.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.18 V (1.74%)235.8 V6.9 V (2.88%)1150.4 WDrop/Amp High
250 kcmil126.7 mm²255 A3.54 V (1.47%)236.5 V5.84 V (2.43%)973.3 WDrop/Amp High
300 kcmil152.0 mm²285 A2.95 V (1.23%)237.0 V4.87 V (2.03%)811.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.53 V (1.05%)237.5 V4.17 V (1.74%)695.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.21 V (0.92%)237.8 V3.65 V (1.52%)608.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.77 V (0.74%)238.2 V2.92 V (1.22%)486.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.48 V (0.61%)238.5 V2.43 V (1.01%)405.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.18 V (0.49%)238.8 V1.95 V (0.81%)324.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.89 V (0.37%)239.1 V1.46 V (0.61%)243.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 125 feet one-way at 240V (1-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 2.95V (1.23%) and delivers 237.0V at the load.

What size aluminum wire is required for 275 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 2.92V (1.22%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.