🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 40 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 0.16%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 0.88V (0.18%)
Voltage at Load End479.2 VLoss: 0.76 V (397.3 W)
Power & Breaker (125%)249.42 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 40 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A65.18 V (13.58%)414.8 V107.51 V (22.4%)33868.0 WDrop/Amp High
12 AWG3.31 mm²20 A40.96 V (8.53%)439.0 V67.56 V (14.08%)21282.6 WDrop/Amp High
10 AWG5.26 mm²30 A25.77 V (5.37%)454.2 V42.52 V (8.86%)13392.7 WDrop/Amp High
8 AWG8.37 mm²50 A16.2 V (3.37%)463.8 V26.72 V (5.57%)8416.4 WDrop/Amp High
6 AWG13.3 mm²65 A10.19 V (2.12%)469.8 V16.81 V (3.5%)5296.6 WDrop/Amp High
4 AWG21.15 mm²85 A6.41 V (1.34%)473.6 V10.57 V (2.2%)3330.8 WDrop/Amp High
3 AWG26.67 mm²100 A5.08 V (1.06%)474.9 V8.39 V (1.75%)2641.4 WDrop/Amp High
2 AWG33.62 mm²115 A4.03 V (0.84%)476.0 V6.65 V (1.39%)2095.3 WDrop/Amp High
1 AWG42.41 mm²130 A3.2 V (0.67%)476.8 V5.27 V (1.1%)1661.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.53 V (0.53%)477.5 V4.18 V (0.87%)1317.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.01 V (0.42%)478.0 V3.32 V (0.69%)1044.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.59 V (0.33%)478.4 V2.63 V (0.55%)828.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.26 V (0.26%)478.7 V2.09 V (0.43%)657.1 WDrop/Amp High
250 kcmil126.7 mm²255 A1.07 V (0.22%)478.9 V1.77 V (0.37%)556.0 WDrop/Amp High
300 kcmil152.0 mm²285 A0.89 V (0.19%)479.1 V1.47 V (0.31%)463.5 WDrop/Amp High
350 kcmil177.3 mm²310 A0.76 V (0.16%)479.2 V1.26 V (0.26%)397.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.67 V (0.14%)479.3 V1.1 V (0.23%)347.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.54 V (0.11%)479.5 V0.88 V (0.18%)278.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.45 V (0.09%)479.6 V0.74 V (0.15%)231.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.36 V (0.07%)479.6 V0.59 V (0.12%)185.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.27 V (0.06%)479.7 V0.44 V (0.09%)139.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 40 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 40 feet one-way at 480V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 0.76V (0.16%) and delivers 479.2V at the load.

What size aluminum wire is required for 300 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 0.88V (0.18%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.