🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 40 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 0.36%
Aluminum Wire (≤3% Drop)2 AWGDrop: 1.77V (0.37%)
Voltage at Load End478.3 VLoss: 1.71 V (236.9 W)
Power & Breaker (125%)66.51 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 40 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A17.38 V (3.62%)462.6 V28.67 V (5.97%)2408.4 WDrop/Amp High
12 AWG3.31 mm²20 A10.92 V (2.28%)469.1 V18.02 V (3.75%)1513.4 WDrop/Amp High
10 AWG5.26 mm²30 A6.87 V (1.43%)473.1 V11.34 V (2.36%)952.4 WDrop/Amp High
8 AWG8.37 mm²50 A4.32 V (0.9%)475.7 V7.12 V (1.48%)598.5 WDrop/Amp High
6 AWG13.3 mm²65 A2.72 V (0.57%)477.3 V4.48 V (0.93%)376.7 WDrop/Amp High
4 AWG21.15 mm²85 A1.71 V (0.36%)478.3 V2.82 V (0.59%)236.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.36 V (0.28%)478.6 V2.24 V (0.47%)187.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.08 V (0.22%)478.9 V1.77 V (0.37%)149.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.85 V (0.18%)479.1 V1.41 V (0.29%)118.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.68 V (0.14%)479.3 V1.11 V (0.23%)93.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.54 V (0.11%)479.5 V0.88 V (0.18%)74.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.43 V (0.09%)479.6 V0.7 V (0.15%)58.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.34 V (0.07%)479.7 V0.56 V (0.12%)46.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.29 V (0.06%)479.7 V0.47 V (0.1%)39.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.24 V (0.05%)479.8 V0.39 V (0.08%)33.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.2 V (0.04%)479.8 V0.34 V (0.07%)28.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.18 V (0.04%)479.8 V0.29 V (0.06%)24.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.14 V (0.03%)479.9 V0.24 V (0.05%)19.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.12 V (0.02%)479.9 V0.2 V (0.04%)16.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.02%)479.9 V0.16 V (0.03%)13.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.07 V (0.01%)479.9 V0.12 V (0.02%)9.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 40 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 40 feet one-way at 480V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 1.71V (0.36%) and delivers 478.3V at the load.

What size aluminum wire is required for 80 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 1.77V (0.37%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.