⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 100 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.65%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 1.72V (0.72%)
Voltage at Load End238.4 VLoss: 1.56 V (946.0 W)
Power & Breaker (125%)145.49 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 100 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A190.11 V (79.21%)49.9 V313.58 V (130.66%)115245.2 WDrop/Amp High
12 AWG3.31 mm²20 A119.46 V (49.78%)120.5 V197.06 V (82.11%)72419.9 WDrop/Amp High
10 AWG5.26 mm²30 A75.17 V (31.32%)164.8 V124.0 V (51.67%)45572.2 WDrop/Amp High
8 AWG8.37 mm²50 A47.24 V (19.68%)192.8 V77.93 V (32.47%)28639.2 WDrop/Amp High
6 AWG13.3 mm²65 A29.73 V (12.39%)210.3 V49.04 V (20.43%)18023.3 WDrop/Amp High
4 AWG21.15 mm²85 A18.7 V (7.79%)221.3 V30.84 V (12.85%)11333.8 WDrop/Amp High
3 AWG26.67 mm²100 A14.83 V (6.18%)225.2 V24.46 V (10.19%)8988.0 WDrop/Amp High
2 AWG33.62 mm²115 A11.76 V (4.9%)228.2 V19.4 V (8.08%)7130.0 WDrop/Amp High
1 AWG42.41 mm²130 A9.32 V (3.88%)230.7 V15.38 V (6.41%)5652.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.39 V (3.08%)232.6 V12.19 V (5.08%)4481.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.86 V (2.44%)234.1 V9.67 V (4.03%)3554.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.65 V (1.94%)235.3 V7.67 V (3.2%)2819.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.69 V (1.54%)236.3 V6.08 V (2.54%)2236.1 WDrop/Amp High
250 kcmil126.7 mm²255 A3.12 V (1.3%)236.9 V5.15 V (2.15%)1891.9 WDrop/Amp High
300 kcmil152.0 mm²285 A2.6 V (1.08%)237.4 V4.29 V (1.79%)1577.0 WDrop/Amp High
350 kcmil177.3 mm²310 A2.23 V (0.93%)237.8 V3.68 V (1.53%)1352.0 WDrop/Amp High
400 kcmil202.7 mm²335 A1.95 V (0.81%)238.0 V3.22 V (1.34%)1182.6 WDrop/Amp High
500 kcmil253.4 mm²380 A1.56 V (0.65%)238.4 V2.57 V (1.07%)946.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.3 V (0.54%)238.7 V2.15 V (0.89%)788.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.04 V (0.43%)239.0 V1.72 V (0.72%)630.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.78 V (0.33%)239.2 V1.29 V (0.54%)473.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 100 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 100 feet one-way at 240V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 1.56V (0.65%) and delivers 238.4V at the load.

What size aluminum wire is required for 350 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 1.72V (0.72%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.