🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 225 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)6× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.34V (27.87%)
Voltage at Load End11.7 VLoss: 0.34 V (118.3 W)
Power & Breaker (125%)4.2 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 225 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A493.91 V (4115.9%)0.0 V814.72 V (6789.31%)172867.8 WDrop/Amp High
12 AWG3.31 mm²20 A310.37 V (2586.43%)0.0 V511.97 V (4266.39%)108629.9 WDrop/Amp High
10 AWG5.26 mm²30 A195.31 V (1627.58%)0.0 V322.17 V (2684.75%)68358.4 WDrop/Amp High
8 AWG8.37 mm²50 A122.74 V (1022.83%)0.0 V202.46 V (1687.19%)42958.8 WDrop/Amp High
6 AWG13.3 mm²65 A77.24 V (643.69%)0.0 V127.41 V (1061.79%)27035.0 WDrop/Amp High
4 AWG21.15 mm²85 A48.57 V (404.78%)0.0 V80.12 V (667.7%)17000.7 WDrop/Amp High
3 AWG26.67 mm²100 A38.52 V (321.0%)0.0 V63.54 V (529.5%)13482.0 WDrop/Amp High
2 AWG33.62 mm²115 A30.56 V (254.64%)0.0 V50.4 V (420.04%)10695.0 WDrop/Amp High
1 AWG42.41 mm²130 A24.22 V (201.86%)0.0 V39.96 V (332.98%)8478.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A19.21 V (160.05%)0.0 V31.68 V (264.01%)6722.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.24 V (126.96%)0.0 V25.13 V (209.43%)5332.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.08 V (100.71%)0.0 V19.93 V (166.12%)4229.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.58 V (79.86%)2.4 V15.81 V (131.73%)3354.2 WDrop/Amp High
250 kcmil126.7 mm²255 A8.11 V (67.57%)3.9 V13.37 V (111.46%)2837.9 WDrop/Amp High
300 kcmil152.0 mm²285 A6.76 V (56.32%)5.2 V11.15 V (92.91%)2365.6 WDrop/Amp High
350 kcmil177.3 mm²310 A5.79 V (48.29%)6.2 V9.56 V (79.65%)2028.0 WDrop/Amp High
400 kcmil202.7 mm²335 A5.07 V (42.24%)6.9 V8.36 V (69.67%)1773.9 WDrop/Amp High
500 kcmil253.4 mm²380 A4.05 V (33.78%)7.9 V6.69 V (55.73%)1419.0 WDrop/Amp High
600 kcmil304.0 mm²420 A3.38 V (28.16%)8.6 V5.57 V (46.45%)1182.8 WDrop/Amp High
750 kcmil380.0 mm²475 A2.7 V (22.53%)9.3 V4.46 V (37.16%)946.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.03 V (16.9%)10.0 V3.34 V (27.87%)709.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 225 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 225 feet one-way at 12V (DC), you need 6× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.82%) and delivers 11.7V at the load.

What size aluminum wire is required for 350 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.34V (27.87%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.