🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 225 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.01%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.19V (9.95%)
Voltage at Load End11.8 VLoss: 0.24 V (30.2 W)
Power & Breaker (125%)1.5 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 225 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A176.4 V (1469.96%)0.0 V290.97 V (2424.75%)22049.5 WDrop/Amp High
12 AWG3.31 mm²20 A110.85 V (923.72%)0.0 V182.85 V (1523.71%)13855.9 WDrop/Amp High
10 AWG5.26 mm²30 A69.75 V (581.28%)0.0 V115.06 V (958.84%)8719.2 WDrop/Amp High
8 AWG8.37 mm²50 A43.84 V (365.3%)0.0 V72.31 V (602.57%)5479.4 WDrop/Amp High
6 AWG13.3 mm²65 A27.59 V (229.89%)0.0 V45.51 V (379.21%)3448.3 WDrop/Amp High
4 AWG21.15 mm²85 A17.35 V (144.56%)0.0 V28.62 V (238.46%)2168.5 WDrop/Amp High
3 AWG26.67 mm²100 A13.76 V (114.64%)0.0 V22.69 V (189.11%)1719.6 WDrop/Amp High
2 AWG33.62 mm²115 A10.91 V (90.94%)1.1 V18.0 V (150.01%)1364.2 WDrop/Amp High
1 AWG42.41 mm²130 A8.65 V (72.09%)3.3 V14.27 V (118.92%)1081.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.86 V (57.16%)5.1 V11.31 V (94.29%)857.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.44 V (45.34%)6.6 V8.98 V (74.8%)680.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.32 V (35.97%)7.7 V7.12 V (59.33%)539.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.42 V (28.52%)8.6 V5.65 V (47.05%)427.8 WDrop/Amp High
250 kcmil126.7 mm²255 A2.9 V (24.13%)9.1 V4.78 V (39.81%)362.0 WDrop/Amp High
300 kcmil152.0 mm²285 A2.41 V (20.12%)9.6 V3.98 V (33.18%)301.7 WDrop/Amp High
350 kcmil177.3 mm²310 A2.07 V (17.24%)9.9 V3.41 V (28.45%)258.7 WDrop/Amp High
400 kcmil202.7 mm²335 A1.81 V (15.08%)10.2 V2.99 V (24.88%)226.3 WDrop/Amp High
500 kcmil253.4 mm²380 A1.45 V (12.07%)10.6 V2.39 V (19.9%)181.0 WDrop/Amp High
600 kcmil304.0 mm²420 A1.21 V (10.06%)10.8 V1.99 V (16.59%)150.9 WDrop/Amp High
750 kcmil380.0 mm²475 A0.97 V (8.05%)11.0 V1.59 V (13.27%)120.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.72 V (6.03%)11.3 V1.19 V (9.95%)90.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 225 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 225 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.24V (2.01%) and delivers 11.8V at the load.

What size aluminum wire is required for 125 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.19V (9.95%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.