⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 200 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.86%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.34V (2.83%)
Voltage at Load End11.7 VLoss: 0.34 V (13.7 W)
Power & Breaker (125%)0.48 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 200 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A50.17 V (418.12%)0.0 V82.76 V (689.71%)2007.0 WDrop/Amp High
12 AWG3.31 mm²20 A31.53 V (262.75%)0.0 V52.01 V (433.41%)1261.2 WDrop/Amp High
10 AWG5.26 mm²30 A19.84 V (165.34%)0.0 V32.73 V (272.74%)793.6 WDrop/Amp High
8 AWG8.37 mm²50 A12.47 V (103.91%)0.0 V20.57 V (171.4%)498.8 WDrop/Amp High
6 AWG13.3 mm²65 A7.85 V (65.39%)4.2 V12.94 V (107.86%)313.9 WDrop/Amp High
4 AWG21.15 mm²85 A4.93 V (41.12%)7.1 V8.14 V (67.83%)197.4 WDrop/Amp High
3 AWG26.67 mm²100 A3.91 V (32.61%)8.1 V6.45 V (53.79%)156.5 WDrop/Amp High
2 AWG33.62 mm²115 A3.1 V (25.87%)8.9 V5.12 V (42.67%)124.2 WDrop/Amp High
1 AWG42.41 mm²130 A2.46 V (20.51%)9.5 V4.06 V (33.83%)98.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.95 V (16.26%)10.0 V3.22 V (26.82%)78.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.55 V (12.9%)10.5 V2.55 V (21.28%)61.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.23 V (10.23%)10.8 V2.03 V (16.88%)49.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.97 V (8.11%)11.0 V1.61 V (13.38%)38.9 WDrop/Amp High
250 kcmil126.7 mm²255 A0.82 V (6.86%)11.2 V1.36 V (11.32%)32.9 WDrop/Amp High
300 kcmil152.0 mm²285 A0.69 V (5.72%)11.3 V1.13 V (9.44%)27.5 WDrop/Amp High
350 kcmil177.3 mm²310 A0.59 V (4.91%)11.4 V0.97 V (8.09%)23.5 W~ ≤5%
400 kcmil202.7 mm²335 A0.51 V (4.29%)11.5 V0.85 V (7.08%)20.6 W~ ≤5%
500 kcmil253.4 mm²380 A0.41 V (3.43%)11.6 V0.68 V (5.66%)16.5 W~ ≤5%
600 kcmil304.0 mm²420 A0.34 V (2.86%)11.7 V0.57 V (4.72%)13.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.27 V (2.29%)11.7 V0.45 V (3.78%)11.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.21 V (1.72%)11.8 V0.34 V (2.83%)8.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 200 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 200 feet one-way at 12V (DC), you need 600 kcmil copper wire. This produces a voltage drop of 0.34V (2.86%) and delivers 11.7V at the load.

What size aluminum wire is required for 40 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.34V (2.83%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.