🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 30 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 0.3V (2.53%)
Voltage at Load End11.7 VLoss: 0.29 V (11.7 W)
Power & Breaker (125%)0.48 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 30 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A7.53 V (62.72%)4.5 V12.41 V (103.46%)301.0 WDrop/Amp High
12 AWG3.31 mm²20 A4.73 V (39.41%)7.3 V7.8 V (65.01%)189.2 WDrop/Amp High
10 AWG5.26 mm²30 A2.98 V (24.8%)9.0 V4.91 V (40.91%)119.0 WDrop/Amp High
8 AWG8.37 mm²50 A1.87 V (15.59%)10.1 V3.09 V (25.71%)74.8 WDrop/Amp High
6 AWG13.3 mm²65 A1.18 V (9.81%)10.8 V1.94 V (16.18%)47.1 WDrop/Amp High
4 AWG21.15 mm²85 A0.74 V (6.17%)11.3 V1.22 V (10.17%)29.6 WDrop/Amp High
3 AWG26.67 mm²100 A0.59 V (4.89%)11.4 V0.97 V (8.07%)23.5 W~ ≤5%
2 AWG33.62 mm²115 A0.47 V (3.88%)11.5 V0.77 V (6.4%)18.6 W~ ≤5%
1 AWG42.41 mm²130 A0.37 V (3.08%)11.6 V0.61 V (5.07%)14.8 W~ ≤5%
1/0 AWG53.49 mm²150 A0.29 V (2.44%)11.7 V0.48 V (4.02%)11.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.23 V (1.93%)11.8 V0.38 V (3.19%)9.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.18 V (1.53%)11.8 V0.3 V (2.53%)7.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.15 V (1.22%)11.9 V0.24 V (2.01%)5.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.12 V (1.03%)11.9 V0.2 V (1.7%)4.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.1 V (0.86%)11.9 V0.17 V (1.42%)4.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.09 V (0.74%)11.9 V0.15 V (1.21%)3.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.08 V (0.64%)11.9 V0.13 V (1.06%)3.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.06 V (0.51%)11.9 V0.1 V (0.85%)2.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.05 V (0.43%)11.9 V0.08 V (0.71%)2.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.34%)12.0 V0.07 V (0.57%)1.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.26%)12.0 V0.05 V (0.42%)1.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 30 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 30 feet one-way at 12V (DC), you need 1/0 AWG copper wire. This produces a voltage drop of 0.29V (2.44%) and delivers 11.7V at the load.

What size aluminum wire is required for 40 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 0.3V (2.53%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.