🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 500 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.23%
Aluminum Wire (≤3% Drop)3 AWGDrop: 13.98V (2.91%)
Voltage at Load End469.3 VLoss: 10.68 V (740.2 W)
Power & Breaker (125%)33.26 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 500 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A108.63 V (22.63%)371.4 V179.19 V (37.33%)7526.2 WDrop/Amp High
12 AWG3.31 mm²20 A68.26 V (14.22%)411.7 V112.6 V (23.46%)4729.5 WDrop/Amp High
10 AWG5.26 mm²30 A42.96 V (8.95%)437.0 V70.86 V (14.76%)2976.1 WDrop/Amp High
8 AWG8.37 mm²50 A27.0 V (5.62%)453.0 V44.53 V (9.28%)1870.3 WDrop/Amp High
6 AWG13.3 mm²65 A16.99 V (3.54%)463.0 V28.02 V (5.84%)1177.0 W~ ≤5%
4 AWG21.15 mm²85 A10.68 V (2.23%)469.3 V17.62 V (3.67%)740.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A8.47 V (1.77%)471.5 V13.98 V (2.91%)587.0 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A6.72 V (1.4%)473.3 V11.09 V (2.31%)465.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A5.33 V (1.11%)474.7 V8.79 V (1.83%)369.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.22 V (0.88%)475.8 V6.97 V (1.45%)292.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.35 V (0.7%)476.6 V5.53 V (1.15%)232.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.66 V (0.55%)477.3 V4.38 V (0.91%)184.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.11 V (0.44%)477.9 V3.48 V (0.72%)146.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.78 V (0.37%)478.2 V2.94 V (0.61%)123.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.49 V (0.31%)478.5 V2.45 V (0.51%)103.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.27 V (0.27%)478.7 V2.1 V (0.44%)88.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.11 V (0.23%)478.9 V1.84 V (0.38%)77.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.89 V (0.19%)479.1 V1.47 V (0.31%)61.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.74 V (0.15%)479.3 V1.23 V (0.26%)51.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.59 V (0.12%)479.4 V0.98 V (0.2%)41.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.45 V (0.09%)479.6 V0.74 V (0.15%)30.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 500 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 500 feet one-way at 480V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 10.68V (2.23%) and delivers 469.3V at the load.

What size aluminum wire is required for 40 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 13.98V (2.91%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.